05.04.2015 Views

PMS-920 - Aplisens SA

PMS-920 - Aplisens SA

PMS-920 - Aplisens SA

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

User manual for meter with U/I input <strong>PMS</strong>-<strong>920</strong><br />

Voltage measurement accuracy<br />

Voltage input resistance<br />

± 0,1% @ 25°C; ± one digit (for 0÷10 V range)<br />

> 50 kΩ<br />

Temperature stability 50 ppm / °C<br />

Display range<br />

-999 ÷ 9999, plus decimal point<br />

Accepted prolonged input overload: 20%<br />

Outputs<br />

relay:<br />

or OC-type:<br />

sensor power supply:<br />

0, 1 or 2 NO, 1A/250V AC (cos ϕ = 1)<br />

0, 1 or 2 30mA / 30VDC / 100mW<br />

24V +5%, -10% / max. 100 mA, stabilized<br />

Communication interface<br />

Baud rate<br />

Display<br />

(depending on version)<br />

Data memory<br />

RS 485, 8N1 and 8N2, Modbus RTU, not separated<br />

1200 bit/s ÷ 115200 bit/s<br />

LED, 4 digit, 13mm height, two-colour (red and green)<br />

or (for IP 65 version) 5 digit, 9mm height, red<br />

non-volatile memory, EEPROM type<br />

Protection level (depending on<br />

display size)<br />

5 x 9mm version: IP 65 (from front), optional version with panel cut-out<br />

sealing available<br />

IP 20 (housing and connection clips)<br />

4 x 13mm version: IP 40 (from front)<br />

IP 20 (housing and connection clips)<br />

Housing type<br />

Housing material<br />

Housing dimensions<br />

Mounting hole<br />

Assembly depth<br />

Panel thickness<br />

Operating temperature<br />

Storage temperature<br />

Humidity<br />

Altitude<br />

panel<br />

NORYL - GFN2S E1<br />

72 x 36 x 97 mm<br />

66.5 x 32.5 mm<br />

min. 102 mm<br />

max. 5 mm<br />

0°C to +50°C<br />

-10°C to +70°C<br />

5 to 90% no condensation<br />

up to 2000 meters above sea level<br />

Screws tightening max. torque 0,5 Nm<br />

Max. connection leads diameter 2,5 mm 2<br />

Safety requirements according to: PN-EN 61010-1<br />

installation category: II<br />

pollution degree: 2<br />

voltage in relation to ground: 300V AC<br />

insulation resistance: >20MΩ<br />

insulation strength between power supply and<br />

input/output terminal: 1min. @ 2300V<br />

insulation strength between relays terminal:<br />

1min. @ 1350V<br />

5

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!