4 The new devices are now<br />

listed in<br />

<strong>CANopen</strong>_<strong>Optimized</strong><br />

To configure the devices,<br />

double click on the specific<br />

item.<br />

<strong>ATV</strong><br />

<strong>CANopen</strong><br />

configuration<br />

1 Double click on the <strong>ATV</strong>_71<br />

or <strong>ATV</strong>_312 to open the<br />

dialog.<br />

Set the Node Id<br />

3x <strong>ATV</strong> 71, node 1..3<br />

4x <strong>ATV</strong> 312, node 4..7<br />

Set the recommended<br />

Heartbeat producer time to<br />

400 ms.<br />

Click on Change Properties<br />

Heartbeat consumer… and<br />

check the time.<br />

Minimum value is:<br />

Heartbeat<br />

producer time x 1.5<br />

(e.g. 400 ms x 1.5 = 600 ms)<br />

Note:<br />

These values depend on the<br />

application<br />

2 Go to<br />

<strong>CANopen</strong> I/O Mapping tab<br />

and check:<br />

Always update variable.<br />