Installation and Operation Manual - Neptronic
Installation and Operation Manual - Neptronic
Installation and Operation Manual - Neptronic
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SKE90/100/110/120 Steam Humidifier<br />
Stage 3 – Water Supply <strong>Installation</strong><br />
!<br />
Water supply installation should conform to local codes <strong>and</strong> regulations.<br />
Any installation work must be carried out by suitably qualified personnel.<br />
Water inlet<br />
Specifications<br />
<strong>Neptronic</strong> ® SKE-XL Humidifier is designed to be used with mains, reverse osmosis, deionized<br />
<strong>and</strong> de-mineralized water.<br />
Maximum water supply pressure: 70 to 480kPa<br />
Minimum water temperature: +4˚C<br />
Maximum water temperature: +40˚C<br />
Model<br />
SKE90<br />
SKE100<br />
SKE110<br />
SKE120<br />
Water inlet<br />
Connection size<br />
Ø 15 mm<br />
Water supply<br />
line <strong>Installation</strong><br />
To facilitate servicing, a shut off valve (not supplied) should be installed in the water<br />
line, within 1m of the humidifier.<br />
Feed Water supply line<br />
¼ turn Shut off Valve<br />
Gasket<br />
Gasket<br />
SKE-XL<br />
Flexible Hose<br />
120 mm<br />
Water Inlet connection<br />
(Illus. 13)<br />
12