SKE90/100/110/120 Steam Humidifier<br />

Stage 3 – Water Supply <strong>Installation</strong><br />

!<br />

Water supply installation should conform to local codes <strong>and</strong> regulations.<br />

Any installation work must be carried out by suitably qualified personnel.<br />

Water inlet<br />

Specifications<br />

<strong>Neptronic</strong> ® SKE-XL Humidifier is designed to be used with mains, reverse osmosis, deionized<br />

<strong>and</strong> de-mineralized water.<br />

Maximum water supply pressure: 70 to 480kPa<br />

Minimum water temperature: +4˚C<br />

Maximum water temperature: +40˚C<br />

Model<br />

SKE90<br />

SKE100<br />

SKE110<br />

SKE120<br />

Water inlet<br />

Connection size<br />

Ø 15 mm<br />

Water supply<br />

line <strong>Installation</strong><br />

To facilitate servicing, a shut off valve (not supplied) should be installed in the water<br />

line, within 1m of the humidifier.<br />

Feed Water supply line<br />

¼ turn Shut off Valve<br />

Gasket<br />

Gasket<br />

SKE-XL<br />

Flexible Hose<br />

120 mm<br />

Water Inlet connection<br />

(Illus. 13)<br />