SKE90/100/110/120 Steam Humidifier<br />
Stage 4 – Water Drain Connection<br />
!<br />
Water Drain<br />
Specification<br />
Water Drain<br />
<strong>Installation</strong><br />
Water Drain installation should conform to local codes <strong>and</strong> regulations.<br />
Any installation work must be carried out by suitably qualified personnel.<br />
Water Drain temperature: 60˚C<br />
Model<br />
SKE90<br />
SKE100<br />
SKE110<br />
SKE120<br />
Water Drain Outlet<br />
Connection size<br />
Ø 20mm<br />
Pan Drain Outlet<br />
Connection size<br />
Ø 15mm<br />
Water drain outlet connection should be connected to drain pipe of sufficient size.<br />
We recommend the use of Ø 20mm minimum st<strong>and</strong>ard copper hydraulic pipes.<br />
Minimum water drain pipe gradient should be 1.5mm in 1m horizontal run.<br />
No drain trap is required.<br />
SKE-XL<br />
Ø 20mm<br />
120mm<br />
Ø 38mm<br />
minimum<br />
(Illus. 14)<br />
13