Utility Structures - Shaw Precast Solutions
Utility Structures - Shaw Precast Solutions
Utility Structures - Shaw Precast Solutions
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
shawprecastsolutions.com<br />
TRANSFORMER PADS<br />
1610x1450 TOP OF FIRE RESISTING BARRIER SINGLE-PHASE PADMOUNT<br />
TRANSFORMER 50kV.A-167kV.A<br />
600<br />
1610<br />
600<br />
50<br />
6-C1502 @ 50<br />
302 c/c<br />
75<br />
475<br />
SEE<br />
DETAIL-A<br />
1450<br />
475<br />
PLAN<br />
500<br />
MIN.<br />
PLAN<br />
C1501 @<br />
75<br />
325 c/c<br />
TRANSFORMER PADS<br />
150<br />
SECTION-A<br />
25mm<br />
CHAMFER<br />
(TYP)<br />
C1501 @<br />
325 c/c<br />
SECTION-A<br />
C1502 @<br />
302 c/c<br />
2-GALV. CHECKER PLATES<br />
10x100x100 WELDED TO A STEEL<br />
PIPE SLEEVE (TOP & BOTTOM).<br />
CHECKER PLATES TO BE DRILLED<br />
WITH 22mmØ HOLE. TOP PLATE<br />
AND CONCRETE TO BE FLUSH.<br />
REBAR SCHEDULE<br />
C1501-#15M BAR x 1500mm LG - 5 REQUIRED<br />
C1502-#15M BAR x 1350mm LG - 6 REQUIRED<br />
25.4mmØ (SCHEDULE 40)<br />
GALV STEEL PIPE SLEEVE<br />
DETAIL-A<br />
19.1mmØ COARSE-THREAD NUT TO<br />
BE WELDED TO BOTTOM PLATE<br />
SHAw precast solutions | UTILITY STRUCTURES > TRANSFORMER PADS 11