FORM <strong>145.05</strong>-<strong>EG1</strong> (0804)<br />
DATA 072 079 090<br />
Capacity Range Min. capacity (tons) 65 70 80<br />
Max. capacity (tons) 100 105 120<br />
Airflow Range Min. VAV design CFM 19,100 21,000 24,000<br />
Max. VAV design & operating CFM 28,700 31,500 36,000<br />
Cabinet Depth (excluding return section) 84 96 96<br />
Dimensions<br />
Length 98 120 120<br />
Height (excluding discharge plenum) 99 99 99<br />
Box type N2 N3 N3<br />
EER Based on ARI 340/360-93 14.6 14.5 14.3<br />
Cooling Coil Face Area 47.8 52.5 60.0<br />
Section<br />
Rows–12 FPI 4 or 6 4 or 6 4 or 6<br />
Waterside Econo Face Area 47.8 52.5 60.0<br />
Section<br />
Rows–12 FPI 2 or 4 2 or 4 2 or 4<br />
Heating Hot Water Heat–Face Area 47.8 52.5 60<br />
Section<br />
Rows–10 FPI 1 or 2 1 or 2 1 or 2<br />
Electric Heat–kW TBD TBD TBD<br />
Steam–Face Area 47.8 52.5 60<br />
Rows–8 FPI 1 1 1<br />
Return Air Filter Type 2” or 4” PLEATED, 12” CARTRIDGE<br />
Section<br />
Filter area 48.9 62.5 62.5<br />
Pre-filter 2” or 4” 2” or 4” 2” or 4”<br />
Efficiency (%) 30–95 30–95 30–95<br />
Final-Filter 4” or 12” 4” or 12” 4” or 12”<br />
Efficiency (%) 65–95 65–95 65–95<br />
Fan Section Type AIRFOIL PLENUM FAN (SWSI)<br />
Quantity–Dia. (in): standard capacity 1–33 1–36 1–36<br />
Quantity–Dia. (in): high capacity 1–36 1–40 1–40<br />
Motor hp range 3.0–40.0 5.0–50.0 5.0–50.0<br />
Compressor Type SCROLL<br />
Section<br />
Quantity 4 4 4<br />
Stages–VAV systems 4–6 4–6 4–6<br />
Condenser Type WATER-COOLED, MECHANICALLY CLEANABLE<br />
Section<br />
Quantity 4 4 4<br />
GPM Range 2.0 to 3.0 GPM/Ton 144–216 158–237 180–270<br />
Due to the dedication of continuous product improvement and enhancements, the information provided<br />
is subject to change without notice.<br />
* Aluminum fins standard. ** M-Available Modular Construction, N- for New Construction<br />
12 YORK INTERNATIONAL