Unit Dimensions 039 to 090<br />

FORM <strong>145.05</strong>-<strong>EG1</strong> (0804)<br />

Model YSWU 039 048 050 & 055 072 079<br />

060 & 090<br />

CFM Range 10,700– 12,700– 14,000– 14,700– 19,100– 21,000–<br />

16,000 19,000 24,000 22,000 28,700 36,000<br />

Tonnage Range 35–55 40–65 40–80 50–75 65–100 70–120<br />

Unit Style Modular Modular New/Retrofit Modular New/Retrofit New/Retrofit<br />

A 1 Fan Section Width 34 34 CF 34 CF CF<br />

B 1 Coil Section Width 34 34 CF 34 CF CF<br />

C 1&3 Installed Width 68 68 82 68 82 94<br />

D Discharge Opening Width 20 20 24 20 24 24 NOTES<br />

E Discharge Opening Length 64 76 72 84 90 112 (see page 25)<br />

F 1 Installed Height 78 78 98 78 98 98<br />

G 1 Electrical Section Width 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8 19 5/8<br />

H Base Length (no panels) 74 86 82 98 96 118<br />

I 2 Installed Length 74 86 82 98 96 118<br />

J Inlet Height 58 1/2 58 1/2 73 1/2 58 1/2 73 1/2 73 1/2<br />

K Inlet Length 60 60 80 60 80 80<br />

L Drain Connection 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8<br />

M Condenser Water Supl/Ret. 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 3 1/8<br />

All dimensions in inches<br />