145.05-EG1 - Johnson Controls
145.05-EG1 - Johnson Controls
145.05-EG1 - Johnson Controls
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
FORM <strong>145.05</strong>-<strong>EG1</strong> (0804)<br />
there is no waterside economizer, and at 50º F<br />
with waterside economizer. At these water temperatures,<br />
the compressor energy consumption<br />
is typically less than 0.5 kW per ton.<br />
Compressor operation at lower condenser<br />
water temperatures is available with condenser<br />
water flow control.<br />
Evaporator coil<br />
This coil, 4 row or 6 row, is row split, with each<br />
refrigerant circuit covering entire coil face in 2-<br />
compressor units. In 4 compressor units, the<br />
coil is row split and has intertwined circuiting to<br />
activate entire coil face when any compressor<br />
is started.<br />
Waterside economizer – Optional<br />
4 row waterside economizer coil is offered as<br />
chemically cleanable or mechanically cleanable.<br />
In either case, the coil is rated for 400 psig<br />
waterside pressure. Waterside economizer<br />
option also includes complete water piping, sensors,<br />
and 2 two-way motorized valves for control<br />
of the economizer cycle. When condenser<br />
water is colder than the mixed air entering the<br />
unit, waterside economizer is activated, allowing<br />
the condenser water through the waterside<br />
economizer coil. If additional cooling is required<br />
to meet the load, condenser water leaving the<br />
economizer coil enters the condenser, and compressors<br />
are turned on as needed.<br />
CONDESNSER WATER PIPING DIAGRAM<br />
mechanical cooling mode only<br />
Water Cooled Condenser<br />
Condenser Water Supply<br />
(CWS)<br />
Condenser Water &<br />
Return (CWR)<br />
Economizer Valve &<br />
Actuator<br />
Bypass Valve & Actuator<br />
Economizer Coil<br />
Evaporator Coil<br />
CONDESNSER WATER PIPING DIAGRAM<br />
economizer with or without mechanical cooling mode<br />
Water Cooled Condenser<br />
Condenser Water Supply<br />
(CWS)<br />
Condenser Water Return<br />
(CWR)<br />
Economizer Valve &<br />
Actuator<br />
Bypass Valve & Actuator<br />
Economizer Coil<br />
Evaporator Coil<br />
FAN SECTION<br />
Plenum fan – quiet, efficient<br />
The YORK Versecon uses an efficient and quiet<br />
airfoil blade backward curve plenum fan, with a<br />
minimum of Class II construction. The fan section<br />
acts as a plenum, keeping discharge velocities<br />
and noise lower, and efficiency high.<br />
Bearing lubrication lines are brought closer to<br />
the front of the unit for easy maintenance.<br />
Vibration isolation<br />
Fan is mounted on vibration isolation springs<br />
and connected on the inlet side with a canvas<br />
flexible connection, minimizing vibration and<br />
noise transmission.<br />
Double wall construction<br />
Unit cabinet in the air stream has double wall<br />
construction with 22 gage perforated liner to<br />
absorb maximum amount of noise and to hold<br />
the insulation permanently in place without use<br />
of studs or glue.<br />
Variable Air volume with unit mounted<br />
and tested VFD – Optional<br />
Variable air volume units include a unit mounted<br />
and tested Variable Frequency Drive on all<br />
460 volt motors and up to 25 HP motors on 208<br />
or 230 volt units. Unit controller adjusts the<br />
VFD speed to maintain static pressure as<br />
sensed by a unit mounted differential air pressure<br />
transducer. The pressure transducer<br />
senses air pressure at an appropriate location<br />
in the supply ductwork through a pressure tube<br />
supplied and installed by others. All VAV units<br />
are supplied with a Duct High Limit pressure<br />
switch to stop the supply fan if the supply air<br />
pressure exceeds the set point.<br />
4 YORK INTERNATIONAL