(4.2)<br />
T 2 : characteristic period, associated to the category of the site and given in the table 4.7<br />
η: is the damping correction factor given by the following formula :<br />
≥ 0.7 4.3<br />
where ζ (%) is the critical damping ratio depending on constitutive material, structure type<br />
and importance of infills.<br />
When ζ=5%, we have η =1.<br />
Infill<br />
Tableau 4.3 : Values of ξ (%)<br />
Frames<br />
Shear walls or walls<br />
Reinforced<br />
concrete<br />
metal<br />
reinforced<br />
concrete/masonry<br />
light 6 4<br />
heavy 7 5<br />
10<br />
- R: global behavior coefficient of the structure, given in table 4.4 according to the lateral<br />
force resisting system as defined in 3.4<br />
In case of different lateral force resisting systems in the two considered directions, the<br />
smallest value of R must be used.<br />
- Q: Quality factor<br />
The quality factor of the structure depends on :<br />
- the redundancy and the geometry of the constituent elements.<br />
- the regularity in plan and in elevation.<br />
- the quality of the control of construction.<br />
The value of Q is determined by the formula :<br />
(4.4)<br />
P q is the penalty to be applied depending on whether the criteria of quality q “ is satisfied or<br />
not”. Its value is given in table 4.4<br />
Criteria of quality “q” to verify are:<br />
1. minimal conditions on bracing plans.<br />
- frames system : every plan of frames must include at all floors, at least three (03) bays and<br />
the ratio of two adjacent spans must not exceed 1.5. The frame bay can be constituted of<br />
shear walls<br />
1-24