This publication is no longer validPlease see http://www-ns.iaea.org/standards/TABLE I. (cont.)Documentation to besubmitted by applicantReference toNUSS documents<strong>International</strong> ornational standards3Additional references4.6. Battery charger System description, design basis D7 — 517-519and specification includingwiring schematic, operationallimits, such as— overvoltage— overcurrent— ripple factor— environmental conditionswhich have to be monitored,list of alarmsKTA 3703 IEEE 323VDE 0510IEEE 4844.7. DC/AC converter Component specification, design D7 — 521, 522 KTA 3704 IEEE 323basis including converter performanceoperational limits, such as— overcurrent— overvoltage— overspeed— frequency deviationwhich have to be monitored,list of alarmsIEC 146 VDE 0160UTEC-96-822