5 Basic system configuration2. Fresh Air Intake Indoor Unit Type34 HP systemConnecting limitation• The total capacity of the fresh air intake units and the indoor units is restricted to 80to 100% against the capacity of the outdoor units.• Up to two fresh air intake units can be connected on one line of the multi system.• The allowable total capacity of fresh air intake units shall be 30% or less againstthe total capacity of the indoor units (including the fresh air intake units).• The fresh air intake units only cannot connected.Capacity codeTotal 34No. of total units8Outdoor unit12HP 12HP 10HP3424 20 16 12 8036(4)036(4)036(4)036(4)036(4)036 Indoor unit(4)10Remotecontroller024 024 Fresh Air Intake Indoor unit(5) (5)Remotecontroller5 -3