6.6.2 Current Sensor DiagnosticsCLASS <strong>3200</strong> METERThe load current must be at least 1% of the meter’s rated load in order to use thediagnostic function. Current sensor diagnostics can detect:1. Reversed current sensors2. Incorrect phase correspondence3. Unusually low power factor (0.642 or lower)CT Error: (ABC) is used to detect the swapping of current sensor phases. Thismessage could (in some rare cases) indicate a low (