CLASS <strong>3200</strong> METER6.7 RS-485 Wiring (continued)* An alternate version of firmware is available that replaces Modbus RTU with BACnetMS/TP. The meter must be ordered with this option if BACnet is desired instead ofModbus.There are two connection methods, daisy-chain and wire terminal, for RS-485communications.Daisy-Chain MethodThis is the simplest method for connecting meters together.M32776Fig. 9. Daisy-chain Configuration.1. Connect the +(high) terminal of PORT 1 of each meter together so that the + terminalson all meters are linked, + to + to +...2. Connect the -(low) terminal of PORT 1 of each meter together so that the - terminalson all meters are linked, - to - to -...3. Connect the GND terminals of PORT 1 to meter 1 ONLY. The GND terminalsshould not be linked to each meter.4. Torque screws to 2.2 in-lb.RS-485TERMINALFig. 10. RS-485 Terminal.M3319562-0390-02 20