12.0 CLASS <strong>3200</strong> PROTOCOL DEFINITIONSModBus Customer Point Map: CL<strong>3200</strong>Address Registers Format Description UnitsCL<strong>3200</strong>40001 1 2 Integer Energy delivered Wh Pulse R/W40001 1 2 Integer Energy received Wh Pulse R/W40005 1 2 Integer Reactive energy delivered VARh Pulse R/W40007 1 2 Integer Reactive energy received VARh Pulse R/W41001 1 2 Float Energy delivered kWh R/W41003 1 2 Float Energy received kWh R/W41005 1 2 Float Reactive energy delivered kVARh R/W41007 1 2 Float Reactive energy received kVARh R/W41009 2 Float Real power kW R41011 2 Float Reactive power kVAR R41013 2 Float Apparent power kVA R41015 2 Float Power factor % PF R41017 2 Float Peak demand kW R41019 2 Float Current average Amps R41021 2 Float Voltage line-neutral Volts-N R41023 2 Float Voltage line-line Volts-L R41025 2 Float Frequency Hz R41027 2 Float Phase angle Degree R41029 2 Float Real power, phase A kW R41031 2 Float Real power, phase B kW R62-0390-02 44