10.07.2015 Views

9010 Intelek-Pro Flow Controller - Georg Fischer Signet LLC

9010 Intelek-Pro Flow Controller - Georg Fischer Signet LLC

9010 Intelek-Pro Flow Controller - Georg Fischer Signet LLC

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

2.4 Standard Output ConnectionsStandard OutputsAn open collector counter pulse output (CNT) anda sensor pulse output (PLS) are included with yourunit.The counter pulse output (synchronous w/totalizer)emits an open collector 150 ms pulse with amaximum current sinking capacity of 50 mA @30 VDC, and is ideal for driving an externalcounter or accumulator. An external DC powersupply and current limiting resistor are requiredfor operation.The sensor pulse output (PLS) emits a standard TTLfrequency output in phase with the sensor inputand can be used to drive +GF+ SIGNETinstruments (except +GF+ SIGNET 5090 and5091) and other TTL compatible devices.SSOUTPUTCNT GND PLSANL2R+ R-SERIALTx GND RxA in SENSORA+ A- BLK RED SHLDFigure 5Sensor pulse output (PLS)/counter output (CNT)wiring1 2 3 4 5 6 7 8 9 10 11 12 13 14ORRed (2)Shld (3)InputGnd+GF+ SIGNETIndicator or<strong>Controller</strong>TTLCompatibleDevice600Ω @ >1.5 WGnd+INGnd5 to 30 VDCPower SupplyExternal counteror accumulatorTo reduce the possibility ofnoise interference, separateoutput lines from AC powerlines.7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!