FireWatch-200 Fire Alarm System Control Unit FA/C -1System SpecificationsEnvironmentalOperating temperature Normal:68 - 77°F (20-25°C)Extreme:32 - 120°F (0-49°C) up to 3 hoursRelative humidityExtreme: 85% @ 86°F up to 24 hoursPrimary Input VoltagePrimary Input Voltage:13200-120: 120 Vac (50/60 Hz)13200-240: 240 Vac (50/60 Hz)Maximum primary input current:13200-120: 1.0 A at 120 Vac13200-240: 0.5A at 240 VacSecondary and Trouble Power Supply24 volt sealed lead-acid battery setMaximum charge voltage: 28 VdcMaximum charge current: 1.5 AMaximum input current: 1.0 ABattery capacity: 7 A.H.Resettable Smoke Detector PowerPower LimitedVoltage: 24 Vdc nominalRipple: 1 V p-p maximumInitiating Device CircuitsPower Limited2 Style "B"/Class B zones minimumStandby voltage range: 16-27 VdcMaximum standby current: 10 mAMaximum standby detector current:3 mA @ 24 VdcMaximum alarm current: 53 mAMaximum ripple: 1 VacMaximum wire loop resistance: 100 ohmsNotification Appliance CircuitsPower LimitedMaximum standby current: 3.4 mAAlarm voltage: 24 Vdc nominalMaximum alarm current: .75 AmpMaximum ripple: 1.5 VacMaximum loop drop voltage: 1.0 VdcOptional City Tie (SCT)Reverse PolarityPower LimitedVoltage: 24 Vdc nominalCurrent: 0.010 Amp maximumRipple: 1 Vac maximumOptional Status Relays (SRM)Power Limited Contact Rating:3.0 Amp, 30 Vdc max. resistive3.0 Amp, 120 Vac max. resistiveMaximum wire loop resistance: 6 ohmsEnclosure ConstructionPainted Steel, RedDimensions9-15/16" (H), 10-3/8" (W), 5-1/4" (D)Ordering InformationCatalog No. Order No. DescriptionFireWatch-200 Control Panel - 2 IDCs, Style "B" (Class B) & 1 NAC, Style "Y" (Class B)FireWatch-200 ..... 13200-0-14-120 ....... Base unit with surface cabinet, 120 VacFireWatch-200 ..... 13200-0-14-240 ....... Base unit with surface cabinet, 240 VacOptions for FireWatch-200 Panel13202 ................... 13202....................... Alarm Relay Module13203 ................... 13203....................... Alarm City Tie Module13209 ................... 13209....................... Semi-Flush Trim15128 ................... DC-100 .................... Digital Communication Sub-Assembly14047 ................... 14047....................... 7.0 Amp/Hr Battery SetPage 2


FireWatch-200 Fire Alarm System Control Unit FA/C -1Typical Wiring3.9K, 1/2WEOL Device(p/n 10808)Smoke/ManualInitiating Device Circuit –Class B, Style BSupervised, TypicalPower Limited24K, 1/2WEOL Device(p/n 10807)Notification ApplianceCircuit – Class B, Style B,Supervised,Typical Power LimitedZone 2 IDC12345678Resettable Auxiliary PowerOutput – Unsupervised, Power-Limited (must not exceed0.1A @ 24 Vdc)Battery LeadsTroubleSilenceAlarmSilenceBattery Set –24V, 7AH, Supervised,Non-Power LimitedInput Current: 1A maxCharge Voltage: 28V maxCharge Current: 1.5A maxSystemResetPage 3


FireWatch-200 Fire Alarm System Control Unit FA/C -1<strong>FARADAY</strong>Faraday, LLC805 South Maumee StreetTecumseh, Michigan 49286Phone: (517) 423-2111Fax: (517) 423-2320Web: www.faradayllc.comWARNING - The information contained in this document is intended only as a summary and issubject to change without notice. The devices described in this document have specificinstruction sheets which cover various technical, limitation and liability information. Copies ofthese instruction sheets and the General Product Warning and Limitations Document, whichalso contains important information, are provided with the product and are available from theManufacturer. Information contained in these documents should be consulted before specifyingor using the product. For further information or assistance concerning particular problemscontact the Manufacturer.Page 4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!