11.07.2015 Views

Feeder Protection Relay REF 610 - APE Distribuidor ABB

Feeder Protection Relay REF 610 - APE Distribuidor ABB

Feeder Protection Relay REF 610 - APE Distribuidor ABB

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Feeder</strong> <strong>Protection</strong> <strong>Relay</strong><strong>REF</strong> <strong>610</strong>Fig. 3 Substation feeder O/C and E/F protection, and substation busbar protection based onRE_ <strong>610</strong> series protection relays. The operate time of the busbar protection has beenspeeded up using the principle of upstream interlockingThe connection of the CTs to the <strong>REF</strong> <strong>610</strong>relay depends on the available number andtypes of CTs in the feeder cubicle. Generallyan outgoing feeder is equipped with threephase current transformers for high- andlow-set overcurrent protection. The residualcurrent for the earth-fault protection can bederived from the three phase currents. It canalso be measured with a ring-type cable currenttransformer, should the outgoing feederbe a cable line and a sensitive earth-faultprotection be required.Should the feeder cubicle be equipped withtwo phase current transformers, the <strong>REF</strong> <strong>610</strong>relay can still be used for high- and low-setovercurrent protection including phase discontinuityand phase unbalance protection.<strong>ABB</strong>