<strong>Product</strong> Data22-1784-052/4YCC3018A through 2/4YCC3060ASingle Packaged Convertible Gas/Electric13 SEER1½ - 5 Ton, 40 - 120 KBTUR-22/R-410A10/08© 2008 Trane Pub. No. 22-1784-05


Single Packaged Convertible Gas/Electric SystemTrane offers a complete family of packaged gas/electric heating and cooling systems,designed to give you the unbeatable combination of energy efficiency andlower operating costs. In warm weather, the package gas/electric system functionsas an all-electric, high efficiency air conditioner. In cold weather, it operates as anatural gas or propane gas furnace, offering you the best of both energy worlds.Introducing the new TRANE Single Packaged ConvertibleGas/Electric System.Single Packaged Convertible Gas/Electric Systems are easy and versatileto install. Because cooling andheating functions are all contained in asingle cabinet, a Trane single packagedconvertible gas/electric system is easy toinstall and service. It can be flushmounted beside your home at groundlevel or placed on the roof for horizontalor downflow installation. When connectedto an optional Trane thermostat control,and air distribution ducts, you have ahighly efficient, total home comfortsystem.Single Packaged Convertible Gas/Electric Systems are unmatched inquality and reliability. All majorcomponents on these products,including the compressor, have beendesigned and manufactured formaximum service. Every Climatuff ®compressor is designed and manufacturedto exacting specifications. Eachdesign is life tested in extreme environmentsto ensure reliable and longlasting operation in normal applications.Each compressor has internal motorprotection for added reliability.Single Packaged Convertible Gas/Electric Systems provide betterperformance. Our single packagedcooling/heating units offer cooling/heating efficiencies that are unmatchedin the industry and provide you with aproduct far superior in performance thanthe competition.2


ContentsOptional Equipment Listing 4General Data 5Performance DataCooling 14Indoor Fan 19Typical Field Wiring 23Typical Wiring 24Optional Equipment 30Dimensional Data 35<strong>Mechanical</strong> Specifications 473


Optional Equipment ListingOPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [✓] indicates accessories included)Hinged Filter Access Door (2/4YCC3018-036) 8 ............................................................. BAYACCDOR1A[ ]Hinged Filter Access Door (2/4YCC3042-060) 8 ............................................................. BAYACCDOR2A[ ]Roof Curb Full Perimeter (2/4YCC3018-36A) 3 ................................................................ BAYCURB050A[ ]Roof Curb Full Perimeter (2/4YCC3042-60A) 3 ................................................................ BAYCURB051A[ ]Roof Curb Utility Extension Kit (BAYCURB050A) ................................................................. BAYUTIL101A[ ]Roof Curb Utility Extension Kit (BAYCURB051A) ................................................................. BAYUTIL102A[ ]0-25% <strong>Manual</strong> Fresh Air Damper (2/4YCC3018-36A) 1. ................................................... BAYOSAH001A[ ]0-25% <strong>Manual</strong> Fresh Air Damper (2/4YCC3042-60A) 1. ................................................... BAYOSAH002A[ ]Motorized Fresh Air Damper (2/4YCC3018-36A) 1. ........................................................ BAYDMPR101A[ ]Motorized Fresh Air Damper (2/4YCC3042-60A) 1. ......................................................... BAYDMPR102A[ ]16" Round Duct Adapter (2 per box) (2/4YCC3018-36A) 6 .............................................. BAYSQRD001A[ ]18" Round Duct Adapter (2 per box) (2/4YCC3018-60A) 6 .............................................. BAYSQRD002A[ ]0-100% Mod Economizer w/Baro. Relief (2/4YCC3018-36A) 124 ................................. BAYECON101B[ ]0-100% Mod. Economizer w/Baro. Relief (2/4YCC042-60A) 124. ................................. BAYECON102B[ ]0-100% Horizontal Economizer (2/4YCC3018-36A) 12 . ................................................ BAYECON200A[ ]0-100% Horizontal Economizer (2/4YCC3042-60A) 12 . ................................................ BAYECON201A[ ]Enthalpy Control for Economizer (solid state). .................................................................... BAYENTH001A[ ]Remote Potentiometer (All-BAYECON***A) ............................................................................ BAYSTAT023[ ]1"-2" Filter Frame (2/4YCC3018-36A) (20 x 25 filter not included) 1. ................................. BAYFLTR101B[ ]1"-2" Filter Frame (2/4YCC3042-60A) (20 x 20,20X18 filter not included) 1. ..................... BAYFLTR201B[ ]LP Conversion Kit (All 40K, 120K Models) ........................................................................... BAYLPKT100A[ ]LP Conversion Kit (All 64K, 96K Models) ............................................................................. BAYLPKT101A[ ]LP Conversion Kit (All 75K Models) ...................................................................................... BAYLPKT102A[ ]Head Pressure Control (Low Ambient Cool) (208/240v) Kit 5. ......................................... BAYLOAM105A[ ]Quick Start Kit (2/4YCC3-A1) .............................................................................................. BAYQSKT301A[ ]Crankcase Heater Recip (2YCC3024,30,42,48A1, 4YCC3018A1)(230v) 5. ..................... BAYCCHT003A[ ]Crankcase Heater Scroll (2YCC3036A1, 4YCC3036,48,60A1/3)(230v) 5. ....................... BAYCCHT202A[ ]Crankcase Heater (4YCC3036,48,60A4)(460v) 5. ............................................................. BAYCCHT203A[ ]Adapter Curb *YC*3018-036A to BAYCURB030,38 ......................................................... BAYADAP050A[ ]Adapter Curb *YC*3018-036A to BAYCURB033 ............................................................... BAYADAP051A[ ]Adapter Curb *YC*3042-060A to BAYCURB030,38 ......................................................... BAYADAP052A[ ]Adapter Curb *YC*3042-060A to BAYCURB033 ............................................................... BAYADAP053A[ ]Adapter Curb *YC*3042-060A to BAYCURB034 ............................................................... BAYADAP054A[ ]12" Duct Shroud Covers Horizontal *YCC3018-060A7. .................................................... BAYCOVR112A[ ]18" Duct Shroud Covers Horizontal *YCC3018-060A 7. .................................................. BAYCOVR118A[ ]Extreme Condition Mounting Kit - All BAYCURB & BAYADAP ......................................... BAYEXMK001A[ ]Extreme Condition Mounting Kit - All BAYUTIL .................................................................. BAYEXMK002B[ ]Extreme Condition Mounting Kit - All Slab Mounts ............................................................. BAYEXMK003A[ ]Lifting Lug Kit .......................................................................................................................... BAYLlFT002B[ ]NOTES:1 Must use filter frame when economizer/fresh air kit is used.2 Dry bulb control standard with economizer.3 Ships knocked down.4 Downflow only.5 Low Ambient cooling requires crankcase heater (BAYCCHT----A).6 It is the responsibility of the installing dealer to properly size the ductwork for each specific application.7 BAYCOVR112,118A will not cover BAYSQRD002A applications8 BAYACCDOR1A requires BAYFLTR101B & BAYACCDOR2A requires BAYFLTR201B. They are not backwardcompatible to BAYFLTR101/201A.4


General DataMODELRATED Volts/PH/HzPerformance Cooling BTUHIndoor Airflow (CFM)Power Input (KW)EER/SEER (BTU/Watt-Hr.)Sound Power Rating [dB(A)]7Performance HeatingInput BTUH (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)POWER CONN.—V/PH/HZMin. Brch. Cir. AmpacityFuse Size — Max. (amps)Fuse Size — Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)REFRIGERANTCharge (lbs.)GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHTShipping (lbs.) / Net (lbs.)4YCC3018A1040A208-230/1/60180006701.68511.0 / 13.0744000079.835 / 651 / #32208-230/1/6010.11515RECIPROCATING208-230/1/606.4 / 38.6SPINE-FIN2 / 2413.323/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23DIRECT / 11/12 / 810208-230/1/600.54 / 0.95CENTRIFUGAL11 X 10DIRECT / 2SEE FAN PERF TABLE1/8 / 825200-230/1/601 / 1.63CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY4.0R410A5.941/2H X W X L45.86 / 44.5 / 52.03471 / 3752YCC3024A1040A208-230/1/60230007252.16211.0 / 13.0744000080.025 / 551 / #32208-230/1/6013.32020RECIPROCATING208-230/1/609.0 / 59.5SPINE-FIN2 / 2413.323/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23DIRECT / 11/12 / 810208-230/1/600.54 / 0.95CENTRIFUGAL11 X 10DIRECT / 2SEE FAN PERF TABLE1/4 / 825200-230/1/601.5 / 2.85CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY4.0R224.51/2H X W X L45.86 / 44.5 / 52.03470 / 3742YCC3024A1064A208-230/1/60230007252.16211.0 / 13.0746400080.035 / 652 / #37208-230/1/6013.32020RECIPROCATING208-230/1/609.0 / 59.5SPINE-FIN2 / 2413.323/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23DIRECT / 11/12 / 810208-230/1/600.54 / 0.95CENTRIFUGAL11 X 10DIRECT / 2SEE FAN PERF TABLE1/4 / 825200-230/1/601.5 / 2.85CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY4.0R224.51/2H X W X L45.86 / 44.5 / 52.03481 / 3854YCC3024A1064A208-230/1/60230007902.0911.0 / 13.0686400079.035 / 652 / #37208-230/1/6016.52525RECIPROCATING208-230/1/608.3 / 57.8SPINE-FIN2 / 2414.693/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23.4DIRECT / 11/12 / 810208-230/1/600.54 / 0.95CENTRIFUGAL10 X 10DIRECT / VARIABLESEE FAN PERF TABLE1/2 / VARIABLE200-230/1/604.3 / 4.3CENTRIFUGALDIRECT / 21/45 / 2800/1500208-230/1/600.34NOTHROWAWAY2.7R410A5.81/2H X W X L45.86 / 44.5 / 52.03481 / 3852YCC3030A1040A208-230/1/602800010252.611.0 / 13.0744000080.025 / 551 / #32208-230/1/6015.72525RECIPROCATING208-230/1/6010.4 / 65.2SPINE-FIN2 / 2413.323/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23DIRECT / 11/12 / 810208-230/1/600.54 / 0.95CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE1/2 / 1030200-230/1/602.1 / 3.28CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY4.0R225.51/2H X W X L45.86 / 44.5 / 52.03470 / 3741Rated in accordance with A.R.I. Standard 210/240. A.R.I. standard rating conditionsare: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoorcoil.2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. Forhigher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.3 Convertible to LPG.4 This value is approximate. For more precise value, see Unit Nameplate.5 Based on U.S. Government Standard Tests.6 Filters must be installed in return air stream. Square footages listed are based on300 f.p.m. face velocity. If permanent filters are used size per manufacturer'srecommendation with a clean resistance of 0.05" W.C.7 Sound Power values are not adjusted for ARI 270-95 tonal corrections.5


General DataMODELRATED Volts/PH/HzPerformance Cooling BTUHIndoor Airflow (CFM)Power Input (KW)EER/SEER (BTU/Watt-Hr.)Sound Power Rating [dB(A)]7Performance HeatingInput BTUH (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)POWER CONN.—V/PH/HZMin. Brch. Cir. AmpacityFuse Size — Max. (amps)Fuse Size — Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)REFRIGERANTCharge (lbs.)GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHTShipping (lbs.) / Net (lbs.)2YCC3030A1064A208-230/1/602800010252.611.0 / 13.0746400080.030 / 602 / #37208-230/1/6015.72525RECIPROCATING208-230/1/6010.4 / 65.2SPINE-FIN2 / 2413.323/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23DIRECT / 11/12 / 810208-230/1/600.54 / 0.95CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE1/2 / 1030200-230/1/602.1 / 3.28CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY4.0R225.51/2H X W X L45.86 / 44.5 / 52.03481 / 3852YCC3030A1075A208-230/1/602800010252.611.0 / 13.0747500079.435 / 652 / #33208-230/1/6015.72525RECIPROCATING208-230/1/6010.4 / 65.2SPINE-FIN2 / 2413.323/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23DIRECT / 11/12 / 810208-230/1/600.54 / 0.95CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE1/2 / 1030200-230/1/602.1 / 3.28CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY4.0R225.51/2H X W X L45.86 / 44.5 / 52.03481 / 3854YCC3030A1075A208-230/1/60280009002.5511.0 / 13.0717500079.530 / 602 / #33208-230/1/6019.23030RECIPROCATING200-230/1/6011.1 / 63SPINE-FIN2 / 2414.693/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23.4DIRECT / 11/6 / 830208-230/1/601.0 / 1.7CENTRIFUGAL10 X 10DIRECT / VARIABLESEE FAN PERF TABLE1/2 / VARIABLE208-230/1/604.3 / 4.3CENTRIFUGALDIRECT / 21/45 / 2800/1500208-230/1/600.34NOTHROWAWAY4.0R410A6.06251/2H X W X L45.86 / 44.5 / 52.03481 / 3852YCC3036A1064A208-230/1/603500012403.15311.0 / 13.0766400080.025 / 552 / #37208-230/1/6023.03535SCROLL208-230/1/6014.7 / 83SPINE-FIN2 / 2413.323/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23DIRECT / 11/5 / 830208-230/1/601.1 / 1.9CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE1/2 / 1075200-230/1/603.5 / 6.7CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY4.0R225.121/2H X W X L45.86 / 44.5 / 52.03479 / 3832YCC3036A1075A208-230/1/603500012403.15311.0 / 13.0767500080.030 / 602 / #33208-230/1/6023.03535SCROLL208-230/1/6014.7 / 83SPINE-FIN2 / 2413.323/8PLATE FIN3 / 153.543/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER23DIRECT / 11/5 / 830208-230/1/601.1 / 1.9CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE1/2 / 1075200-230/1/603.5 / 6.7CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY4.0R225.121/2H X W X L45.86 / 44.5 / 52.03479 / 3831Rated in accordance with A.R.I. Standard 210/240. A.R.I. standard rating conditionsare: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoorcoil.2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. Forhigher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.3 Convertible to LPG.4 This value is approximate. For more precise value, see Unit Nameplate.5 Based on U.S. Government Standard Tests.6 Filters must be installed in return air stream. Square footages listed are based on300 f.p.m. face velocity. If permanent filters are used size per manufacturer'srecommendation with a clean resistance of 0.05" W.C.7 Sound Power values are not adjusted for ARI 270-95 tonal corrections.6


General DataMODELRATED Volts/PH/HzPerformance Cooling BTUHIndoor Airflow (CFM)Power Input (KW)EER/SEER (BTU/Watt-Hr.)Sound Power Rating [dB(A)]7Performance HeatingInput BTUH (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)POWER CONN.—V/PH/HZMin. Brch. Cir. AmpacityFuse Size — Max. (amps)Fuse Size — Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)REFRIGERANTCharge (lbs.)GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHTShipping (lbs.) / Net (lbs.)2YCC3048A1096A208-230/1/604700016504.27211.0 / 13.0779600080.030 / 603 / #37208-230/1/6029.04545RECIPROCATING208-230/1/6018.6 / 93.4SPINE-FIN2 / 2420.543/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1075200-230/1/604.4 / 8.8CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R2291/2H X W X L49.86 / 47.4 / 61.75653 / 5352YCC3048A1120A208-230/1/604700016504.27211.0 / 13.07712000080.040 / 703 / #32208-230/1/6029.04545RECIPROCATING208-230/1/6018.6 / 93.4SPINE-FIN2 / 2420.543/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1075200-230/1/604.4 / 8.8CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R2291/2H X W X L49.86 / 47.4 / 61.75659 / 5414YCC3048A1075A208-230/1/604650016004.25211.0 / 13.0807500080.020 / 502 / #33208-230/1/6031.55050SCROLL208-230/1/6020.5 / 109SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1075200-230/1/604.4 / 8.8CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75645 / 5174YCC3048A1096A208-230/1/604650016004.25211.0 / 13.0809600080.030 / 603 / #37208-230/1/6031.55050SCROLL208-230/1/6020.5 / 109SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1075200-230/1/604.4 / 8.8CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75653 / 5254YCC3048A1120A208-230/1/604650016004.25211.0 / 13.08012000080.040 / 703 / #32208-230/1/6031.55050SCROLL208-230/1/6020.5 / 109SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1075200-230/1/604.4 / 8.8CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75659 / 5311Rated in accordance with A.R.I. Standard 210/240. A.R.I. standard rating conditionsare: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoorcoil.2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. Forhigher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.3 Convertible to LPG.4 This value is approximate. For more precise value, see Unit Nameplate.5 Based on U.S. Government Standard Tests.6 Filters must be installed in return air stream. Square footages listed are based on300 f.p.m. face velocity. If permanent filters are used size per manufacturer'srecommendation with a clean resistance of 0.05" W.C.7 Sound Power values are not adjusted for ARI 270-95 tonal corrections.10


General DataMODELRATED Volts/PH/HzPerformance Cooling BTUHIndoor Airflow (CFM)Power Input (KW)EER/SEER (BTU/Watt-Hr.)Sound Power Rating [dB(A)]7Performance HeatingInput BTUH (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)POWER CONN.—V/PH/HZMin. Brch. Cir. AmpacityFuse Size — Max. (amps)Fuse Size — Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)REFRIGERANTCharge (lbs.)GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHTShipping (lbs.) / Net (lbs.)4YCC3048A3075A208-230/3/604650016004.25211.0 / 13.0807500080.020 / 502 / #33208-230/3/6024.03535SCROLL208-230/3/6014.6 / 91SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1075200-230/1/604.4 / 8.8CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75645 / 5174YCC3048A3096A208-230/3/604650016004.25211.0 / 13.0809600080.030 / 603 / #37208-230/3/6024.03535SCROLL208-230/3/6014.6 / 91SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1075200-230/1/604.4 / 8.8CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75653 / 5254YCC3048A3120A208-230/3/604650016004.25211.0 / 13.08012000080.040 / 703 / #32208-230/3/6024.03535SCROLL208-230/3/6014.6 / 91SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1075200-230/1/604.4 / 8.8CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75659 / 5314YCC3048A4075A460/3/604650016004.25211.0 / 13.0807500080.020 / 502 / #33460/3/6011.71515SCROLL460/3/607.1 / 46SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825460/1/600.74 / 1.6CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1080460/1/602.2 / 4.36CENTRIFUGALDIRECT / 11/35 / 3480460/1/600.25NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75645 / 5174YCC3048A4096A460/3/604650016004.25211.0 / 13.0809600080.030 / 603 / #37460/3/6011.71515SCROLL460/3/607.1 / 46SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825460/1/600.74 / 1.6CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1080460/1/602.2 / 4.36CENTRIFUGALDIRECT / 11/35 / 3480460/1/600.25NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75653 / 5251Rated in accordance with A.R.I. Standard 210/240. A.R.I. standard rating conditionsare: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoorcoil.2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. Forhigher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.3 Convertible to LPG.4 This value is approximate. For more precise value, see Unit Nameplate.5 Based on U.S. Government Standard Tests.6 Filters must be installed in return air stream. Square footages listed are based on300 f.p.m. face velocity. If permanent filters are used size per manufacturer'srecommendation with a clean resistance of 0.05" W.C.7 Sound Power values are not adjusted for ARI 270-95 tonal corrections.11


MODELRATED Volts/PH/HzPerformance Cooling BTUHIndoor Airflow (CFM)Power Input (KW)EER/SEER (BTU/Watt-Hr.)Sound Power Rating [dB(A)]7Performance HeatingInput BTUH (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)POWER CONN.—V/PH/HZMin. Brch. Cir. AmpacityFuse Size — Max. (amps)Fuse Size — Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)REFRIGERANTCharge (lbs.)GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHTShipping (lbs.) / Net (lbs.)4YCC3048A4120A460/3/604650016004.25211.0 / 13.08012000080.040 / 703 / #32460/3/6011.71515SCROLL460/3/607.1 / 46SPINE-FIN2 / 2418.013/8PLATE FIN3 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825460/1/600.74 / 1.6CENTRIFUGAL10 X 10DIRECT / 2SEE FAN PERF TABLE3/4 / 1080460/1/602.2 / 4.36CENTRIFUGALDIRECT / 11/35 / 3480460/1/600.25NOTHROWAWAY5.3R410A8.21/2H X W X L47.86 / 47.4 / 61.75659 / 531General Data2YCC3060A1096A208-230/1/605800018505.11411.0 / 13.0799600080.025 / 553 / #37208-230/1/6040.66060SCROLL208-230/1/6025 / 148SPINE-FIN2 / 2423.073/8PLATE FIN4 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/3 / 825208-230/1/601.7 / 3.6CENTRIFUGAL11 X 10DIRECT / 3SEE FAN PERF TABLE1 / 1075208-230/1/607.6 / 7.4CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R2291/2H X W X L51.86 / 47.4 / 61.75678 / 5502YCC3060A1120A208-230/1/605800018505.11411.0 / 13.07912000080.030 / 603 / #32208-230/1/6040.66060SCROLL208-230/1/6025 / 148SPINE-FIN2 / 2423.073/8PLATE FIN4 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/3 / 825208-230/1/601.7 / 3.6CENTRIFUGAL11 X 10DIRECT / 3SEE FAN PERF TABLE1 / 1075208-230/1/607.6 / 7.4CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R2291/2H X W X L51.86 / 47.4 / 61.75684 / 5564YCC3060A1096A208-230/1/605800018005.47810.95 / 13.0799600080.025 / 553 / #37208-230/1/6043.56060SCROLL208-230/1/6027.6 / 158SPINE-FIN2 / 2420.543/8PLATE FIN4 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL11 X 10DIRECT / 3SEE FAN PERF TABLE1 / 1075208-230/1/607.6 / 7.4CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A101/2H X W X L49.86 / 47.4 / 61.75678 / 5504YCC3060A1120A208-230/1/605800018005.47810.95 / 13.07912000080.030 / 603 / #32208-230/1/6043.56060SCROLL208-230/1/6027.6 / 158SPINE-FIN2 / 2420.543/8PLATE FIN4 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL11 X 10DIRECT / 3SEE FAN PERF TABLE1 / 1075208-230/1/607.6 / 7.4CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A101/2H X W X L49.86 / 47.4 / 61.75678 / 5501Rated in accordance with A.R.I. Standard 210/240. A.R.I. standard rating conditionsare: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoorcoil.2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. Forhigher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.3 Convertible to LPG.4 This value is approximate. For more precise value, see Unit Nameplate.5 Based on U.S. Government Standard Tests.6 Filters must be installed in return air stream. Square footages listed are based on300 f.p.m. face velocity. If permanent filters are used size per manufacturer'srecommendation with a clean resistance of 0.05" W.C.7 Sound Power values are not adjusted for ARI 270-95 tonal corrections.12


MODELRATED Volts/PH/HzPerformance Cooling BTUHIndoor Airflow (CFM)Power Input (KW)EER/SEER (BTU/Watt-Hr.)Sound Power Rating [dB(A)]7Performance HeatingInput BTUH (Natural Gas)AFUETemp. Rise — Min/Max (°F)Orifice Qty / Drill Size (Natural Gas)POWER CONN.—V/PH/HZMin. Brch. Cir. AmpacityFuse Size — Max. (amps)Fuse Size — Recmd. (amps)COMPRESSORVolts/Ph/HzR.L. Amps — L.R. AmpsOUTDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)INDOOR COIL — TYPERows/F.P.I.Face Area (sq.ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.)OUTDOOR FAN — TYPEDia. (in.)Drive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsINDOOR FAN — TYPEDia x Width (in.)Drive/No. SpeedsCFM @ 0.0 in. w.g.Motor — HP/R.P.M.Volts/Ph/HzF.L. Amps/L.R. AmpsCOMBUSTION FAN — TYPEDrive/No. SpeedsMotor — HP/R.P.M.Volts/Ph/HzFLAFILTER / FURNISHEDType RecommendedRecmd. Face Area (sq. ft.)REFRIGERANTCharge (lbs.)GAS PIPE SIZE (in.)DIMENSIONSCrated (in.)WEIGHTShipping (lbs.) / Net (lbs.)4YCC3060A3096A208-230/3/605800018005.47810.95 / 13.0799600080.025 / 553 / #37208-230/3/6031.75050SCROLL208-230/3/6018.1 / 137SPINE-FIN2 / 2420.543/8PLATE FIN4 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL11 X 10DIRECT / 3SEE FAN PERF TABLE1 / 1075208-230/1/607.6 / 7.4CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A101/2H X W X L49.86 / 47.4 / 61.75678 / 550General Data4YCC3060A3120A208-230/3/605800018005.47810.95 / 13.07912000080.030 / 603 / #32208-230/3/6031.75050SCROLL208-230/3/6018.1 / 137SPINE-FIN2 / 2420.543/8PLATE FIN4 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/601.4 / 3.5CENTRIFUGAL11 X 10DIRECT / 3SEE FAN PERF TABLE1 / 1075208-230/1/607.6 / 7.4CENTRIFUGALDIRECT / 11/35 / 3480208-230/1/600.53NOTHROWAWAY5.3R410A101/2H X W X L49.86 / 47.4 / 61.75684 /5564YCC3060A4096A460/3/605800018005.47810.95 / 13.0799600080.025 / 553 / #37460/3/6019.52525SCROLL460/3/608.97 / 62SPINE-FIN2 / 2420.543/8PLATE FIN4 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/600.74 / 1.6CENTRIFUGAL11 X 10DIRECT / 3SEE FAN PERF TABLE1 / 1075208-230/1/607.6 / 7.4CENTRIFUGALDIRECT / 11/35 / 3480460/1/600.25NOTHROWAWAY5.3R410A101/2H X W X L49.86 / 47.4 / 61.75678 / 5504YCC3060A4120A460/3/605800018005.47810.95 / 13.07912000080.030 / 603 / #32460/3/6019.52525SCROLL460/3/608.97 / 62SPINE-FIN2 / 2420.543/8PLATE FIN4 / 1553/8EXPANSION VALVE3/4 FEMALE NPTPROPELLER27.6DIRECT / 11/4 / 825208-230/1/600.74 / 1.6CENTRIFUGAL11 X 10DIRECT / 3SEE FAN PERF TABLE1 / 1075208-230/1/607.6 / 7.4CENTRIFUGALDIRECT / 11/35 / 3480460/1/600.25NOTHROWAWAY5.3R410A101/2H X W X L49.86 / 47.4 / 61.75684 / 5561Rated in accordance with A.R.I. Standard 210/240. A.R.I. standard rating conditionsare: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoorcoil.2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. Forhigher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.3 Convertible to LPG.4 This value is approximate. For more precise value, see Unit Nameplate.5 Based on U.S. Government Standard Tests.6 Filters must be installed in return air stream. Square footages listed are based on300 f.p.m. face velocity. If permanent filters are used size per manufacturer'srecommendation with a clean resistance of 0.05" W.C.7 Sound Power values are not adjusted for ARI 270-95 tonal corrections.13


Performance Data Cooling2YCC3024A AT 800 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 22.2 14.3 17.2 20 21.9 1.9185 63 23.2 13.1 15.8 18.4 20.1 1.9267 25.0 11.3 13.6 15.9 17.3 1.9571 27.0 9.4 11.3 13.2 14.4 1.9759 20.6 13.6 16.3 19.0 20.6 2.0795 63 21.5 12.5 15.0 17.5 19.1 2.0967 23.2 10.8 12.9 15.1 16.5 2.1271 25.0 8.9 10.7 12.5 13.7 2.1459 19.1 12.8 15.4 18 19.1 2.24105 63 19.9 11.8 14.1 16.5 18.0 2.2567 21.4 10.1 12.2 14.2 15.5 2.2971 23.1 8.4 10.1 11.8 12.9 2.3159 17.5 12.0 14.4 16.8 17.5 2.40115 63 18.2 11.0 13.2 15.4 16.9 2.4167 19.6 9.5 11.4 13.3 14.6 2.4571 21.2 7.9 9.5 11.0 12.1 2.48CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 700 0.98 0.97HIGH 900 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 23000 BTUHAIRFLOW = 725 CFMCOMPRESSOR POWER = 1790 WATTSI.D. FAN POWER = 201 WATTSO.D. FAN POWER = 100 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.2YCC3030A AT 1000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 26.8 18.0 21.6 25.2 26.8 2.2885 63 27.9 16.5 19.8 23.1 25.3 2.2967 30.1 14.2 17.1 19.9 21.8 2.3371 32.5 11.8 14.2 16.5 18.1 2.3559 24.9 17.2 20.7 24.1 24.9 2.4895 63 25.9 15.8 19.0 22.1 24.2 2.4967 27.9 13.6 16.4 19.1 20.9 2.5371 30.2 11.3 13.6 15.9 17.3 2.5659 23.0 16.4 19.7 23.0 23.0 2.68105 63 23.9 15.0 18.1 21.1 23.0 2.7067 25.8 13.0 15.6 18.2 19.9 2.7471 27.9 10.8 12.9 15.1 16.5 2.7759 21.1 15.5 18.6 21.1 21.1 2.88115 63 22.0 14.2 17.1 19.9 21.8 2.9067 23.7 12.3 14.7 17.2 18.8 2.9571 25.5 10.2 12.2 14.3 15.6 2.98CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 875 0.98 0.97HIGH 1125 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 28000 BTUHAIRFLOW = 1025 CFMCOMPRESSOR POWER = 2094 WATTSI.D. FAN POWER = 335 WATTSO.D. FAN POWER = 116 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.2YCC3036A AT 1200 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 32.8 22.5 27.1 31.6 32.8 2.8285 63 34.2 20.7 24.9 29.0 31.7 2.8467 36.9 17.8 21.4 25.0 27.3 2.8871 39.8 14.8 17.8 20.7 22.7 2.9159 31.1 21.8 26.2 30.5 31.1 3.0995 63 32.4 20.0 24.0 28.0 30.6 3.1167 34.9 17.2 20.7 24.2 26.4 3.1671 37.7 14.3 17.2 20.0 21.9 3.1959 29.3 21.0 25.2 29.3 29.3 3.37105 63 30.6 19.3 23.1 27.0 29.5 3.3967 33.0 16.6 20.0 23.3 25.4 3.4471 35.6 13.8 16.6 19.3 21.1 3.4859 27.6 20.1 24.2 27.6 27.6 3.64115 63 28.8 18.5 22.2 25.9 28.3 3.6667 31.0 15.9 19.2 22.3 24.4 3.7271 33.5 13.2 15.9 18.5 20.3 3.76CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 1050 0.98 0.97HIGH 1350 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 35000 BTUHAIRFLOW = 1240 CFMCOMPRESSOR POWER = 2535 WATTSI.D. FAN POWER = 428 WATTSO.D. FAN POWER = 219 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.14


2YCC3042A AT 1400 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 38.3 25.5 30.6 35.7 38.3 3.2885 63 40 23.4 28.1 32.7 35.8 3.3167 43.1 20.2 24.2 28.2 30.9 3.3671 46.5 16.7 20.1 23.4 25.6 3.3959 35.6 24.4 29.3 34.2 35.6 3.5595 63 37.1 22.4 26.9 31.4 34.3 3.5867 40.0 19.3 23.2 27.1 29.6 3.6471 43.2 16.0 19.3 22.5 24.6 3.6759 32.9 23.2 27.9 32.6 32.9 3.82105 63 34.3 21.3 25.6 29.9 32.7 3.8567 36.9 18.4 22.1 25.8 28.2 3.9171 39.9 15.3 18.4 21.4 23.4 3.9559 30.2 22.0 26.4 30.2 30.2 4.09115 63 31.4 20.2 24.2 28.2 30.9 4.1267 33.9 17.4 20.9 24.4 26.6 4.1971 36.6 14.4 17.4 20.2 22.1 4.23CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 1225 0.98 0.97HIGH 1575 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 40000 BTUHAIRFLOW = 1400 CFMCOMPRESSOR POWER = 2823 WATTSI.D. FAN POWER = 502 WATTSO.D. FAN POWER = 311 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.2YCC3048A AT 1600 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 45.5 30.6 36.8 42.9 45.5 3.8485 63 47.4 28.1 33.8 39.3 43.0 3.8767 51.1 24.2 29.1 34.0 37.1 3.9371 55.2 20.1 24.2 28.2 30.8 3.9759 41.7 29.3 35.2 41.0 41.7 4.1595 63 43.5 26.9 32.3 37.6 41.1 4.1867 46.9 23.2 27.9 32.5 35.5 4.2571 50.6 19.2 23.1 26.9 29.4 4.2959 38 27.7 33.3 38.0 38.0 4.46105 63 39.6 25.4 30.6 35.6 38.9 4.4967 42.7 21.9 26.4 30.7 33.6 4.5771 46.1 18.2 21.9 25.5 27.9 4.6159 34.2 25.9 31.2 34.2 34.2 4.77115 63 35.7 23.8 28.6 33.3 35.7 4.8067 38.4 20.5 24.7 28.8 31.4 4.8871 41.5 17.0 20.5 23.9 26.1 4.93CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 1400 0.98 0.97HIGH 1800 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 47000 BTUHAIRFLOW = 1650 CFMCOMPRESSOR POWER = 3387 WATTSI.D. FAN POWER = 589 WATTSO.D. FAN POWER = 297 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.2YCC3060A AT 2000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 54.7 36.6 44.0 51.3 54.7 4.7485 63 57.0 33.6 40.4 47.1 51.5 4.7767 61.4 29.0 34.9 40.6 44.4 4.8571 66.3 24.1 28.9 33.7 36.9 4.8959 52.0 35.5 42.7 49.8 52.0 5.2295 63 54.2 32.6 39.2 45.7 49.9 5.2567 58.4 28.1 33.8 39.4 43.1 5.3471 63.0 23.4 28.1 32.7 35.8 5.3959 49.2 34.4 41.3 48.2 49.2 5.69105 63 51.3 31.5 37.9 44.2 48.3 5.7367 55.3 27.2 32.7 38.1 41.7 5.8271 59.7 22.6 27.2 31.6 34.6 5.8859 46.5 33.1 39.8 46.4 46.5 6.17115 63 48.5 30.4 36.6 42.6 46.6 6.2167 52.3 26.2 31.5 36.8 40.2 6.3171 56.4 21.8 26.2 30.5 33.3 6.37CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 1750 0.98 0.97HIGH 2250 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 58000 BTUHAIRFLOW = 1850 CFMCOMPRESSOR POWER = 4417 WATTSI.D. FAN POWER = 563 WATTSO.D. FAN POWER = 293 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.15


Performance Data Cooling4YCC3018A AT 600 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 17.5 11.4 13.7 16.0 17.5 1.4385 63 18.2 10.5 12.6 14.7 16.1 1.4467 19.7 9.1 10.9 12.7 13.9 1.4671 21.2 7.5 9.0 10.5 11.5 1.4859 15.9 10.7 12.9 15.0 15.9 1.5795 63 16.6 9.8 11.8 13.8 15.1 1.5867 17.8 8.5 10.2 11.9 13.0 1.6071 19.3 7.0 8.5 9.9 10.8 1.6259 14.3 9.9 11.9 13.9 14.3 1.70105 63 14.9 9.1 10.9 12.8 13.9 1.7167 16.0 7.9 9.4 11.0 12.0 1.7471 17.3 6.5 7.8 9.1 10.0 1.7659 12.6 9.1 10.9 12.6 12.6 1.84115 63 13.2 8.3 10.0 11.7 12.7 1.8567 14.2 7.2 8.6 10.1 11.0 1.8871 15.3 6.0 7.2 8.3 9.1 1.90CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 525 0.98 0.97HIGH 675 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 18000 BTUHAIRFLOW = 675 CFMCOMPRESSOR POWER = 1291 WATTSI.D. FAN POWER = 236 WATTSO.D. FAN POWER = 109 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.4YCC3024A1 AT 800 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)OD ID TOT SENS CAP AT ENTERING DB TEMP TOTALAMB WB CAP 72 75 78 80 KW859510511559 22.9 19.1 21.4 22.9 22.9 1.863 23.9 15.6 17.9 20.2 21.8 1.867 25.8 12.3 14.7 17.0 18.6 1.971 27.8 9.1 11.5 13.8 15.3 1.959 20.9 18.2 20.5 20.9 20.9 2.063 21.8 14.7 17.0 19.3 20.9 2.067 23.5 11.5 13.8 16.1 17.7 2.071 25.3 8.3 10.6 12.9 14.5 2.059 18.8 17.3 18.8 18.8 18.8 2.163 19.6 13.8 16.1 18.5 19.6 2.167 21.1 10.6 12.9 15.3 16.8 2.271 22.8 7.4 9.7 12.1 13.6 2.259 16.7 16.4 16.7 16.7 16.7 2.363 17.5 13.0 15.3 17.5 17.5 2.367 18.8 9.8 12.1 14.4 16.0 2.371 20.3 6.6 8.9 11.2 12.8 2.3USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIERLOW 700 0.97 0.98HIGH 900 1.03 1.02ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER790 23400 14.00 11.60ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WBair entering indoor coil, 95°F DB air entering outdoor coil. (B) High TemperatureHeating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoorcoil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°FDB air entering indoor coil. (D) Rated indoor airflow for heating is the same as forcooling.4YCC3030A1 AT 1000 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)OD ID TOT SENS CAP AT ENTERING DB TEMP TOTALAMB WB CAP 72 75 78 80 KW859510511559 29.8 24.1 26.9 29.2 28.9 2.363 31.0 19.7 22.6 25.5 27.4 2.367 33.4 15.8 18.6 21.5 23.4 2.371 36.1 11.8 14.6 17.5 19.4 2.359 27.3 23.0 25.8 27.3 27.3 2.563 28.5 18.7 21.5 24.4 26.3 2.567 30.7 14.7 17.6 20.4 22.3 2.571 33.1 10.7 13.6 16.5 18.4 2.559 24.8 21.9 24.7 24.8 24.8 2.763 25.9 17.6 20.5 23.3 25.2 2.767 27.9 13.7 16.5 19.4 21.3 2.771 30.1 9.7 12.6 15.4 17.4 2.759 22.4 20.8 22.4 22.4 22.4 2.963 23.3 16.6 19.5 22.3 23.3 2.967 25.1 12.7 15.5 18.4 20.3 2.971 27.1 8.7 11.6 14.4 16.4 2.9USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIERLOW 875 0.97 0.98HIGH 1125 1.03 1.02ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER890 30000 14.00 12.00ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WBair entering indoor coil, 95°F DB air entering outdoor coil. (B) High TemperatureHeating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoorcoil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°FDB air entering indoor coil. (D) Rated indoor airflow for heating is the same as forcooling.16


4YCC3036A AT 1200 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 33.2 22.3 26.8 31.2 33.2 2.8085 63 34.6 20.5 24.6 28.7 31.3 2.8167 37.3 17.7 21.2 24.7 27.0 2.8671 40.3 14.7 17.6 20.5 22.4 2.8959 31.2 21.4 25.7 29.9 31.2 3.1195 63 32.5 19.6 23.6 27.5 30.0 3.1367 35.0 16.9 20.3 23.7 25.9 3.1871 37.8 14.0 16.9 19.7 21.5 3.2159 29.1 20.4 24.5 28.5 29.1 3.42105 63 30.3 18.7 22.5 26.2 28.6 3.4567 32.7 16.1 19.4 22.6 24.7 3.5071 35.3 13.4 16.1 18.7 20.5 3.5459 27.0 19.3 23.2 27.0 27.0 3.74115 63 28.2 17.7 21.3 24.8 27.1 3.7667 30.4 15.3 18.4 21.4 23.4 3.8271 32.8 12.7 15.2 17.8 19.4 3.86CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 1050 0.98 0.97HIGH 1350 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 35000 BTUHAIRFLOW = 1200 CFMCOMPRESSOR POWER = 2557 WATTSI.D. FAN POWER = 417 WATTSO.D. FAN POWER = 208 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.4YCC3042A1 AT 1400 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)OD ID TOT SENS CAP AT ENTERING DB TEMP TOTALAMB WB CAP 72 75 78 80 KW859510511559 40.3 34.1 38.4 40.3 40.3 3.163 42.0 27.7 31.9 36.2 39.0 3.167 45.3 21.8 26.1 30.3 33.2 3.271 48.9 15.9 20.2 24.4 27.3 3.259 37.6 32.9 37.2 37.6 37.6 3.463 39.2 26.6 30.8 35.1 37.9 3.567 42.2 20.7 24.9 29.2 32.0 3.571 45.6 14.8 19.1 23.3 26.2 3.559 34.9 31.7 34.9 34.9 34.9 3.863 36.4 25.4 29.7 33.9 36.4 3.867 39.2 19.6 23.8 28.1 30.9 3.871 42.3 13.7 18.0 22.2 25.1 3.859 32.2 30.5 32.2 32.2 32.2 4.163 33.6 24.3 28.6 32.8 33.6 4.167 36.2 18.5 22.7 26.9 29.8 4.271 39.0 12.6 16.8 21.1 23.9 4.2USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOWAIR FLOW CAPACITY TOTAL POWERRATE, CFM MULTIPLIER MULTIPLIERLOW 1225 0.97 0.98HIGH 1575 1.03 1.02ARI RATING FOR COOLINGCFM CAPACITY (A) TEST SEER EER1360 42000 14.25 12.00ARI Standard Capacity Rating ConditionsARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WBair entering indoor coil, 95°F DB air entering outdoor coil. (B) High TemperatureHeating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoorcoil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°FDB air entering indoor coil. (D) Rated indoor airflow for heating is the same as forcooling.4YCC3048A AT 1600 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 43.8 29.8 35.8 41.7 43.8 3.7485 63 45.6 27.3 32.9 38.3 41.9 3.7767 49.2 23.6 28.4 33.1 36.1 3.8371 53.1 19.6 23.5 27.4 30.0 3.8759 41.4 28.8 34.6 40.3 41.4 4.1395 63 43.2 26.4 31.7 37.0 40.4 4.1667 46.5 22.8 27.4 31.9 34.9 4.2371 50.2 18.9 22.7 26.5 28.9 4.2759 39.0 27.7 33.3 38.8 39.0 4.52105 63 40.7 25.4 30.5 35.6 38.9 4.5567 43.8 21.9 26.3 30.7 33.6 4.6371 47.3 18.2 21.9 25.5 27.8 4.6759 36.6 26.5 31.9 36.6 36.6 4.91115 63 38.2 24.3 29.2 34.1 37.2 4.9467 41.2 21.0 25.2 29.4 32.1 5.0271 44.4 17.4 20.9 24.4 26.7 5.07CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 1400 0.98 0.97HIGH 1800 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 46500 BTUHAIRFLOW = 1599 CFMCOMPRESSOR POWER = 3322 WATTSI.D. FAN POWER = 592 WATTSO.D. FAN POWER = 313 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 11.00 BTUH/WATTALL TEMPERATURES IN DEGREES F.17


Performance Data Cooling4YCC3060A AT 2000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 75 78 80 KW59 56.1 36.3 43.6 50.9 55.6 4.7485 63 58.5 33.3 40.0 46.7 51.0 4.7767 63.1 28.7 34.6 40.3 44.0 4.8571 68.1 23.9 28.7 33.4 36.5 4.8959 52.1 34.8 41.8 48.7 52.1 5.2795 63 54.3 31.9 38.4 44.7 48.9 5.3067 58.5 27.6 33.1 38.6 42.2 5.3971 63.2 22.9 27.5 32 35.0 5.4459 48.0 33.1 39.8 46.4 48.0 5.80105 63 50.1 30.4 36.5 42.6 46.5 5.8367 54.0 26.2 31.5 36.7 40.2 5.9371 58.3 21.8 26.2 30.5 33.3 5.9959 44.0 31.3 37.6 43.8 44.0 6.33115 63 45.8 28.7 34.5 40.2 43.9 6.3767 49.4 24.7 29.7 34.7 37.9 6.4771 53.3 20.5 24.7 28.8 31.4 6.53CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR)AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITYLOW 1750 0.98 0.97HIGH 2250 1.02 1.03VALUES AT ARI RATING CONDITIONSTOTAL NET CAPACITY = 58000 BTUHAIRFLOW = 1800 CFMCOMPRESSOR POWER = 4402 WATTSI.D. FAN POWER = 607 WATTSO.D. FAN POWER = 288 WATTSS.E.E.R. = 13.00 BTUH/WATTE.E.R = 10.95 BTUH/WATTALL TEMPERATURES IN DEGREES F.18


Indoor Fan Performance 2/4YCC3018AHorizontal AirflowIndoor Blower Performance2/4YC*3018A1-HOREXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 149 147 142 138 - - - - - - -CFM 688 631 547 461 - - - - - - -HIGHWATTS - 269 259 247 233 220 208 - - - -CFM - 1049 981 897 794 674 549 - - - -Down Airflow2/4YC*3018A1-DOWNEXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 148 143 141 137 - - - - - - -CFM 668 593 515 440 - - - - - - -HIGHWATTS 275 264 254 244 232 218 205 - - - -CFM 1066 989 927 852 750 626 502 - - - -Indoor Fan Performance 2YCC3024AHorizontal Airflow2YC*3024A1HOREXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 215 212 205 195 186 - - - - - -CFM 831 796 743 677 602 - - - - - -HIGHWATTS - - 358 345 327 302 277 266 - - -CFM - - 1239 1165 1056 898 720 593 - - -Down Airflow2YC*3024A1-DOWNEXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 215 208 201 193 183 - - - - - -CFM 812 766 721 662 583 - - - - - -HIGHWATTS 377 367 351 331 310 291 274 262 - - -CFM 1331 1274 1193 1090 966 829 686 547 - - -Indoor Fan Performance 2YCC3030AHorizontal Airflow2YC*3030A1-HOREXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 358 345 339 331 319 301 - - - - -CFM 1218 1149 1103 1052 979 879 - - - - -HIGHWATTS - - - 467 450 434 415 390 - - -CFM - - - 1330 1248 1158 1048 901 - - -Down Airflow2YC*3030A1-DOWNEXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 353 345 336 325 312 297 - - - - -CFM 1176 1136 1080 1012 933 839 - - - - -HIGHWATTS - - - 463 443 424 404 381 - - -CFM - - - 1296 1201 1093 969 822 - - -19


Indoor Fan Performance 2/4YCC3036AHorizontal Airflow2/4YC*3036A-HOREXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 470 448 434 420 402 378 351 - - - -CFM 1332 1292 1240 1177 1100 1007 896 - - - -HIGHWATTS - 670 651 634 616 595 569 536 498 - -CFM - 1542 1472 1426 1364 1267 1135 989 869 - -Down AirflowIndoor Blower Performance2/4YC*3036A-DOWNEXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 460 445 431 416 400 381 358 - - - -CFM 1267 1257 1198 1124 1050 966 843 - - - -HIGHWATTS - 713 694 676 657 636 612 588 - - -CFM - 1584 1502 1420 1327 1221 1100 970 - - -Indoor Fan Performance 2YCC3042AHorizontal Airflow2YC*3042A1-HOREXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 543 540 532 522 511 499 484 461 - - -CFM 1490 1490 1471 1444 1415 1382 1339 1272 - - -HIGHWATTS - 633 624 602 580 562 547 525 480 - -CFM - 1715 1695 1640 1584 1539 1497 1428 1284 - -Down Airflow2YC*3042A1-DOWNEXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 548 523 517 512 497 472 446 440 - - -CFM 1525 1467 1449 1429 1386 1320 1250 1215 - - -HIGHWATTS - 611 597 583 567 549 529 507 482 - -CFM - 1680 1646 1606 1559 1505 1441 1366 1277 - -Indoor Fan Performance 2/4YCC3048AHorizontal Airflow2/4YC*3048A1 -HOREXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWHIGHDown Airflow2/4YC*3048A1 -DOWNEXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWHIGHWATTS 687 668 649 628 606 581 551 516 - - -CFM 1863 1810 1760 1708 1648 1577 1493 1391 - - -WATTS - 935 921 886 851 825 803 773 708 - -CFM - 2159 2110 2017 1919 1833 1753 1652 1482 - -WATTS 671 650 632 614 594 571 543 512 - - -CFM 1839 1795 1741 1682 1622 1554 1472 1362 - - -WATTS - 901 879 857 835 813 787 754 708 - -CFM - 2080 2013 1943 1872 1797 1709 1590 1418 - -20


Indoor Fan Performance 2/4YCC3060AIndoor Blower PerformanceHorizontal Airflow2/4YC*3060A1-HOREXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 500 498 513 532 548 559 568 582 - - -CFM 1884 1873 1842 1806 1772 1743 1716 1685 - - -MEDIUMWATTS 657 650 659 677 696 714 729 741 752 767 -CFM 2052 2056 2035 2002 1967 1935 1907 1878 1841 1783 -HIGHWATTS - 780 790 802 816 831 846 860 870 874 -CFM - 2184 2151 2128 2103 2069 2030 1994 1979 2012 -Down Airflow2/4YC*3060A1-DOWNEXTERNAL STATIC PRESSURE (IN. WG)MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0LOWWATTS 499 511 525 540 553 565 578 593 - - -CFM 1873 1850 1816 1779 1742 1709 1676 1639 - - -MEDIUMWATTS 661 670 684 698 712 725 737 749 764 785 -CFM 2071 2034 2001 1970 1941 1912 1881 1844 1799 1740 -HIGHWATTS - 800 819 826 834 848 866 875 859 790 -CFM - 2158 2123 2092 2063 2034 2000 1961 1911 1849 -Indoor Fan Performance 4YCC3024AHorizontal Airflow4YC*3024A-HORMotor SpeedDown AirflowLOWMED*HIGHExternal Static Pressure (in. wg)0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1Watts 52 66 89 115 140 164 186 206 229 259 300CFM 706 716 727 733 731 719 700 679 662 659 682Watts - 94 120 148 177 207 233 254 267 290 320CFM - 793 805 813 813 806 793 780 778 799 800Watts - - 125 153 182 211 243 284 342 426 551CFM - - 877 892 903 904 897 884 869 863 8774YC*3024A-DOWNMotor SpeedLOWMED*HIGH*Factory Default SettingExternal Static Pressure (in. wg)0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1Watts 35 70 90 108 131 160 188 204 240 270 320CFM 695 729 734 728 721 715 705 679 675 680 685Watts 79 87 105 129 155 180 206 232 264 306 364CFM 846 807 802 810 816 813 803 794 800 820 810Watts 86 102 127 156 185 213 242 275 319 345 385CFM 884 870 882 899 909 907 895 886 898 910 90021


Indoor Fan Performance 4YCC3030AHorizontal Airflow4YC*3030A-HORExternal Static Pressure (in. wg)Motor Speed0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1350 CFM400 CFM*450 CFMWattsWattsWatts---113146195148184233176215267203243303233272340263303371291330388309348373306347-267312----CFMCFMCFM---88099611229051009113291710131134918101211369131008113890610031133901100011079079971039930994-979991----Down Airflow4YC*3030A-DOWNExternal Static Pressure (in. wg)Motor Speed0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1350 CFMWatts - 112 147 172 198 227 259 288 303 286 217 -CFM - 871 894 898 893 884 874 864 851 828 788 -400 CFM*Watts - 152 185 211 238 269 303 333 349 334 271 -CFM - 990 995 992 984 974 964 955 946 937 925 -450 CFMWatts - 191 227 258 289 321 355 392 432 - - -CFM - 1090 1099 1095 1091 1091 1089 1071 1011 - - -Indoor Fan Performance 4YCC3042AHorizontal Airflow4YC*3042A-HORMotor Speed350 CFM400 CFM*450 CFMDown Airflow4YC*3042A-DOWNMotor Speed350 CFM400 CFM*450 CFMExternal Static Pressure (in. wg)0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1Watts - 160 185 214 245 277 308 339 368 396 423CFM - 1206 1211 1213 1215 1215 1214 1212 1208 1201 1190Watts - 231 261 292 325 359 394 431 467 503 536CFM - 1389 1398 1405 1409 1410 1408 1403 1399 1396 1399Watts - 326 362 393 421 450 482 517 556 597 -CFM - 1582 1592 1593 1587 1577 1566 1557 1553 1556 -External Static Pressure (in. wg)0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1Watts - 176 203 232 262 294 325 357 388 417 443CFM - 1207 1214 1217 1216 1213 1208 1201 1193 1185 1177Watts - 253 290 323 355 386 420 455 491 526 558CFM - 1405 1411 1413 1412 1407 1399 1389 1377 1366 1357Watts - 367 379 409 446 485 522 556 591 633 -CFM - 1599 1577 1570 1569 1566 1560 1550 1537 1528 -AFUE Ratings2/4YCC AFUE RatingsAll YCC3018A through YCC3060A units are rated at 80.0AFUE with the following exceptions:2YCC3030A1075 is rated at 79.4 AFUE4YCC3018A1040 is rated at 79.8 AFUE4YCC3024A1064 is rated at 79.0 AFUE4YCC3030A1075 is rated at 79.5 AFUE22


Typical Field WiringUNIT CONTROL BOXBGYW1W2RCOMMONFAN (GR)COMPRESSORHEAT FIRST STAGEHEAT SECOND STAGE24V(WH)(WH)GROUNDWIRE1 PHPOWER3 PHPOWERUNITNOTE 1BGYW1W2RCOMMONFAN(GR)COMPRESSORHEAT FIRST STAGEHEAT SECOND STAGE24V(WH)(WH)BG(GR)YW1 (WH)W2 (WH)RC 757192i223


Typical wiringModels 4YCC3018, 2YCC3024, 2YCC3030, 2/4YCC3036, 2YCC3042, 2/4YCC3048, and 2/4YCC3060See Service Facts for detailed wiring diagrams of the individual models24


Typical wiringModels 4YCC3018, 2YCC3024, 2YCC3030, 2/4YCC3036, 2YCC3042, 2/4YCC3048, and 2/4YCC3060See Service Facts for detailed wiring diagrams of the individual models25


Typical wiringModels 4YCC3024 and 4YCC3030IMPORTANT: Retain this wiring diagram; please return this document to service information pack upon completion of work.26


Typical wiringModels 4YCC3024 and 4YCC3030IMPORTANT: Retain this wiring diagram; please return this document to service information pack upon completion of work.27


Typical wiringModel 4YCC3042IMPORTANT: Retain this wiring diagram; please return this document to service information pack upon completion of work.28


Typical wiringModel 4YCC3042IMPORTANT: Retain this wiring diagram; please return this document to service information pack upon completion of work.29


Optional EquipmentBAYCURB050A Full Perimeter Roof Mounting Curb for 2/4YCC3018-036A17 7/846 3/833 5/819 1/22 3/161519 1/238 7/8141 1/2The drawings on this page areprepared by the manufacturer in orderto provide detail regarding job layoutonly. These drawings are not intendedto be used as a basis to construct,build or modify the items depicted inthe drawings. The manufacturer is notresponsible for the unauthorized useof these drawings and expresslydisclaims any liability for damagesresulting from such unauthorized use.35 7/843 3/830


Optional EquipmentBAYCURB051A Full Perimeter Roof Mounting Curb for 2/4YCC3042-060A15 7/856 1/831 1/22019 1/24 3/410 7/841 7/819 1/214The drawings on this page areprepared by the manufacturer in orderto provide detail regarding job layoutonly. These drawings are not intendedto be used as a basis to construct,build or modify the items depicted inthe drawings. The manufacturer is notresponsible for the unauthorized useof these drawings and expresslydisclaims any liability for damagesresulting from such unauthorized use.38 7/8 53 1/831


Optional EquipmentBAYECON101,102A Down Discharge Economizer and Rain Hood(Mounts Over Horizontal Return Air Opening)AHVAC UnitEconomizerrain hoodEconomizer Unit ApplicationM odels AMisteliminatorOutside airdampersReturnairdampersRequired filterkit, orderseparatelyBAYECON101ABAYECON102A2/4YC,WC3018-036A4TC*3018-036A4W/T/Y/DCY4024-0602/4YC,WC3042-060A4TC*3042-060A4W/T/Y/DCY4024-06020.125"24.375"ReliefdamperRoofcurbReturnDuctBAYECON200,201A Horizontal Economizer and Rain HoodThe drawings on this pageare prepared by themanufacturer in order toprovide detail regarding joblayout only. These drawingsare not intended to be usedas a basis to construct,build or modify the itemsdepicted in the drawings.The manufacturer is notresponsible for the unauthorizeduse of thesedrawings and expresslydisclaims any liability fordamages resulting fromsuch unauthorized use.EconomizerCABDGaskets (2)DuctERain HoodMixed Air SensorEconomizer A B C D EBAYECON200AA 22" 20" 16-7/8" 15-11/16 11-11/16BAYECON201AA 26" 22-21/32" 19" 17-11/16 14-11/1632


Optional EquipmentBAYOSAH001,002A, 25% Outside Air Damper(Replaces Filter/Coil Access Panel)The drawings on this page are preparedby the manufacturer in order to providedetail regarding job layout only. Thesedrawings are not intended to be used asa basis to construct, build or modify theitems depicted in the drawings. Themanufacturer is not responsible for theunauthorized use of these drawings andexpressly disclaims any liability fordamages resulting from such unauthorizeduse.DCAFULLYOPEN2/31/3BFULLYCLOSED<strong>Manual</strong> FreshAir ModelBAYOSAH001BAYOSAH002Unit ApplicationModels2/4YC,WC3018-036A4TC*3018-036A4W/T/Y/DCY4024-036A4W/Y/DCZ6036A2/4YC,WC3042-060A4TC*3042-060A4W/T/Y/DCY4042-0604W/Y/DCZ6048-060AA B C D22 7/16" 20 11/16" 12 3/8" 9 3/16"25 3/16" 20 11/16" 12 3/8" 9 3/16"BAYDMPR101,102A, 25% Motorized Outside Air Damper(Mounts Over Horizontal Return AIr Opening)ACBEBAYDMPR101ABAYDMPR102AUnit ApplicationModels2/4YC,WC3018-036A4TC3018-036A4W/T/Y/DCY4024-036A4W/Y/DCZ6036A2/4YC,WC3042-060A4TC3042-060A4W/T/Y/DCY4042-060A4W/Y/DCZ6048-060AA B C D E15 13/16" 11 13/16" 10 1/4" 11 1/2" 12 1/4"18 3/16" 15 1/8" 10 1/4" 11 1/2" 12 1/4"D33


Optional EquipmentBAYFLTR101, 201B, 1" - 2" Filter Rack(Mounts in Filter/Coil Section)FilterBAYACCDOR1A & BAYACCDOR2A Hinged Filter Access DoorReplaces Filter/Coil Access PanelThe drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawingsare not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is notresponsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from suchunauthorized use.34


Dimensional Data and WeightsModels 4YCC3018, 2YCC3024, 2YCC3030, and 2/4YCC3036Figure 1. YCC3018A through YCC3036A (1 of 3)35


Dimensional Data and WeightsModels 4YCC3018, 2YCC3024, 2YCC3030, and 2/4YCC3036Figure 2. YCC3018A through YCC3036A (2 of 3)36


Dimensional Data and WeightsModels 4YCC3018, 2YCC3024, 2YCC3030, and 2/4YCC3036Figure 3. YCC3018A through YCC3036A (3 of 3)37


Dimensional Data and WeightsModels 2YCC3042, 2/4YCC3048, 2/4YCC3060Figure 4. YCC3042A through YCC3060A (1 of 3)38


Dimensional Data and WeightsModels 2YCC3042, 2/4YCC3048, 2/4YCC3060Figure 5. YCC3042A through YCC3060A (2 of 3)39


Dimensional Data and WeightsModels 2YCC3042, 2/4YCC3048, 2/4YCC3060Figure 6. YCC3042A through YCC3060A (3 of 3)40


Dimensional Data and WeightsModels 4YCC3024, and 4YCC3030Figure 7. 4YCC3024A and 4YCC3030A (1 of 3)41


Dimensional Data and WeightsModels 4YCC3024, and 4YCC3030Figure 8. 4YCC3024A and 4YCC3030A (2 of 3)42


Dimensional Data and WeightsModels 4YCC3024, and 4YCC3030Figure 9. 4YCC3024A and 4YCC3030A (3 of 3)43


Dimensional Data and WeightsModel 4YCC3042Figure 10. 4YCC3042A (1 of 3)44


Dimensional Data and WeightsModel 4YCC3042Figure 11. 4YCC3042A (2 of 3)45


Dimensional Data and WeightsModel 4YCC3042Figure 12. 4YCC3042A (3 of 3)46


<strong>Mechanical</strong> SpecificationsGeneralAll units shall be factory assembled, piped,internally wired and fully charged withrefrigerant. All units shall be designed tooperate at outdoor ambient temperaturesas high as 115°F Cooling capacities shallbe rated in accordance with A.R.I.standards. The YC heating/cooling unitdesign is UL listed, specifically for outdoorapplications using natural gas or propane.All units shall be designed for outdoorrooftop or ground level installation. Unitcasing is constructed of heavy gauge,galvanized steel and painted with aweather-resistant powder paint.Shipped for horizontal application,convertible to downflow.CasingsAll panels shall be heavy gauge steel,gasketed and insulated. Foil-faced fiberinsulation shall be in the heat exchangersection. Foil-faced insulation shall be in theevaporator section. Base pan shall beheavy gauge steel. WEATHERGUARDexterior corrosion resistant screws shall beused for added resistance to rust andcorrosion.ControlsRefrigeration cycle controls shall includecondenser fan, evaporator fan andcompressor contactors. Compressors shallbe equipped with a combination internalwinding thermostat/current overload.Internal high pressure relief shall also beprovided.Refrigeration SystemCompressors —The Climatuff ® compressor featuresinternal over temperature and pressureprotector, total dipped hermetic motor.Other features include: roto lock suctionand discharge refrigeration connections,centrifugal oil pump, and low vibration andnoise.Evaporator Coil — Internally enhanced3/8-inch OD seamless copper tubingmechanically bonded to aluminum fins,factory pressure and leak tested at 250 to300 psig. All units have TXV to controlrefrigeration flow.Condenser Coil —The Spine Fincondenser coil shall becontinuously wrapped, corrosion resistantall aluminum with minimum brazed joints.This coil is 3/8 inch O.D. seamless aluminumtubing glued to a continuous aluminumfin. Coils are lab tested to withstand2,000 pounds of pressure per square inch.The outdoor coil provides low airflowresistance and efficient heat transfer. Thecoil is protected on all four sides bylouvered panels.Indoor Air Fan — Direct-drive, forwardcurved,centrifugal wheel in a CompositeVortica ® Blower housing. Motor shall havethermal overload protection. Permanentlylubricated motor bearings. Motor/blowerassembly isolated from unit with rubbermounts.Condenser Fan — Direct-drive, draw thrupropeller type. Weather-proofed permanentsplit capacitor fan motor shall have built-inthermal overload and permanentlylubricated motor bearings.Low Ambient — Standard refrigerantsystem operation down to 55°F. Lowambient accessory required for operationto 0°F ambient condition.Heating SystemGas-Fired Heating Section — Modelsshall provide completely assembled, wiredand piped gas fired heating systems withinunit. Design certified by UL, specifically foroutdoor application. Threaded gasconnection on the unit.Electronic Ignition System — Mainburner is lit each time thermostat calls forheat. Flame sensor proves flame andkeeps the main burners on. Should a lossof flame occur, the main valve closes andthe spark recurs within 0.8 second. Whenthermostat is satisfied, main burner isextinguished.Forced Combustion Blower — Insuresflame stability under varying windconditions. Gives higher combustionefficiency and location flexibility.Heat Exchanger — stainless steeltubes. Free floating design.Burners — stainless steel. Multiportinshot.Downflow Accessories(U.S. Domestic Models)Roof Curb — The roof curb shallbe designed to mate with the unitand provide support and completeweather-tight installation whenproperly installed. Curb shall shipknocked down for field assembly,and include wood nailer strips.EconomizerModulating Economizer — Thisaccessory shall be field installedand be composed of the followingitems: 0-100% fresh air damper,damper drive motor fixed dry bulbenthalpy control, and low voltagepolarized plug for electricalconnections. Solid state enthalpy ordifferential enthalpy control isoptional. Economizer operationsshall be controlled by the presetposition of the enthalpy control. Abarometic relief damper shall bestandard with the economizer andprovide a pressure operateddamper that shall be gravity closingand prohibit entrance of outside airon equipment “off” cycle.<strong>Manual</strong> Fresh Air Hood<strong>Manual</strong> outside air provides a fixedoutside air quantity from 0 to 25percent. Includes hood andbirdscreen.Low Ambient ControlControl allows cycling ofcompressor under low ambientcooling conditions. Required forcooling operation to 0°F.Propane GasConversion Kit — For conversionfrom natural gas to LP gas.47


Trane6200 Troup HighwayTyler, TX 75707Trane has a policy of continuous product and product data improvement and it reserves the right to changedesign and specifications without notice.48