4-5-5 In case of heating at the cooling mode or cooling at the heating mode1. Troubleshooting procedureMEMOIs the Thermo off?YesChange the setting temperature ofremote control.NoIs the unitin the defrosting operation?YesOperate it with a heating modeas soon as the defrosting is finished.NoIs the compressorin 3 minutes off?YesAfter 3 minutes, coolingand heating start automatically.NoIs much frostin the indoor heatexchanger?YesIs theoutdoor air sensor andoutdoor heat exchanger attachedcorrectly?NoAttach thesensor correctly.NoYesOver shortageof the refrigerantDoes the4-WAY valve operatenormally?NoIs the4-WAY valve connectorconnected correctly?NoConnect the connectercorrectly.YesCheck the resistance valueof 4-WAY valve coil.NG4-WAY valve coil errorOKDose thevoltage of AC220Vapply to the connector of 4-WAYvalve coil during theoperation?NoExchangethe outdoor PCB.YesGo to the next page4-WAY valve main body errorSamsung Electronics 4-21CH£ª£ª£ªCAV_USA_30520_SM_N.indd 21 2009-2-18 17:33:44