LaserFOCUS VLF-250 Product Guide - Pertronic Industries Ltd
LaserFOCUS VLF-250 Product Guide - Pertronic Industries Ltd
LaserFOCUS VLF-250 Product Guide - Pertronic Industries Ltd
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
VESDA ®<strong>LaserFOCUS</strong> <strong>VLF</strong>-<strong>250</strong> <strong>Product</strong> <strong>Guide</strong>Extra terminals (Terminals 3, 4, 5, 6 & 7)Terminals reserved for future use.Legend3 Display Tx4 Display Rx5 Display Comm Gnd6 Display Power -7 Display Power +Figure 9 - Terminal block display, spare power terminalsPower supply (Terminals 8, 9, 10 & 11)Operating voltage:Power consumption:Current consumption:24 VDC nominal (18 - 30 VDC)5.2 W nominal, 7.0 W in alarm220 mA nominal, 295 mA in alarmIt is recommended that the power supply be compliant with local codes and standards requiredby the regional authority. For code specific information see page ii.Caution:Check the product termination wiring label during installation and subsequentmaintenance visits.Legend8 Power Return 0 VDC From power supply unit9 Power in 24 VDC10 Power Return 0 VDC To next detector (if morethan 1 detector per Power11 Power Out 24 VDC Supply Unit)Figure 10 - Terminal block display, power supply9