VESDA ®<strong>LaserFOCUS</strong> <strong>VLF</strong>-<strong>250</strong> <strong>Product</strong> <strong>Guide</strong>Area Covered<strong>250</strong> m 2 (<strong>250</strong>0 sq. ft.)Field WiringAccessTerminals3 x 25 mm (1 in.) Cable entries (1 rear entry)0.2 mm 2 - 2.5 mm 2 (30 - 12 AWG)InterfacesPower In/Out.Fire 1 Relay (changeover, 2A @ 30 VDC).Action Relay (changeover, 2A @ 30 VDC).Fault Relay (changeover, 2A @ 30 VDC).General Purpose Input (clean contact).External display port (with power limited output).RS232 programming port.Alarm RangesAlert, ActionFire 1, Fire 2Individual Delays0.025 – 2.0% obs/m (0.008 – 0.625% obs/ft.)*0.025 – 20% obs/m (0.008 – 6.25% obs/ft.)*0 - 60 seconds2 Threshold sets (1 & 2) Day and nightFor code specific information see page ii.Display4 Alarm State Indicators.Fault and Disabled Indicators.Smoke Level Indicators.Instant Fault Finder.Reset, Disable and Test Controls.Smoke and Flow AutoLearn Controls and Indicators.33