OfficeIndustryDataCenter147Acceptance measurement Class FVarioKeystone® 4K7/ELine 1200® EC7The measuring device is set to the measuringbandwidth of 600 MHz for the acceptance measurementaccording to Class F.Refer to the instructions on setting the measuring device.Information can be found under:www.idealindustries.de/www.flukenetworks.comMake sure that the measuring adapter is connected to themeasuring device and firmly engaged. Take the correspondingmeasuring cable and make sure that it is firmly plugged in.If synchronisation is required, this is then carried out accordingto the instructions for the device.Standard acceptance: Channel or permanent linkStandard acceptance: Channel or permanent linkVarioKeystone® 4K7Ideal LanTEK II/7G(available from Ideal Industries)EC7 measuring adapter(channel)(available from Ideal Industries)Measuring cable set(Order no.: LKD 9ZE3 0053 0000)ELine 1200® EC7Ideal LanTEK II/7G(available from Ideal Industries)EC7 measuring adapter (channel)(available from Ideal Industries)Measuring cable set(Order no.: 9ZE30057)ELine 1200® EC7 Fluke DTX 1800(available from Fluke Networks)EC7 measuring adapter (permanent link)(Order no.: 9ZE30038)SystemApprovedmeasuring devicesApprovedmeasuring adaptersApprovedmeasuring cableswww.leoni-infrastructure-datacom.com