Table 1. Spill Fire Test ResultsTest #<strong>Foam</strong> TypeTest DescriptionHeptane FuelFlow rateShielded FireSolution Flow;l/min<strong>Foam</strong>Distribution;litres/min/m2Fire SizeMwExtinguishmenttime; min:s99% 100%1 CAF B, 2% 11 l/ min no (confined to 4.65m2) 90 1.63 4.65m2) 90 1.63 6 1:05 1:285 CAF B, 2% 22.5 l/ min yes ( unconfined >13m2) 90 1.63 11.5 1:26 1:386 CAF B, 2% 22.5 l/ min yes ( unconfined >13m2) 90 1.63 11.5 1:55 4:587 CAF Milspec B, 2% 22.5 l/ min yes ( unconfined >13m2) 90 1.63 11.5 1:45 4:208 FWS ClassB, 3% 22.5 l/ min yes ( unconfined >13m2) 360 6.5 11.5 1:30 not ext.9 FWS Milspec B, 3% 22.5 l/ min yes ( unconfined >13m2) 360 6.5 11.5 2:00 not ext.8