UMG 508Mode (absolute)If a scanning value exceeds the set limit value, atransient is recognized.• Off- Transient monitoring is switched off• Automatic- Factory pre-setting. The limit valueis automatically calculated and is 110% ofthe current 200 ms effective value.• Manual- Transient monitoring uses the adjustablelimit value under "Peak U“.Mode (delta)If the difference of two neighbouring scanningpoints exceeds the set limit value, a transient isrecognized.• Off- Transient monitoring is switched off.• Automatic- Factoring pre-setting. The limitvalue is calculated automatically and is 0.2175times the current 200ms effective value.• Manual- Transient monitoring uses the adjustablelimit value under "Trns U“.Accept L2-L4Transient monitoring can be set per phase. Youcan accept settings from phase L1 into phasesL2, L3 and L4.• No - The L1 phase settings are not transferredto the stages L2, L3 and L4.• Yes- The settings from phase L1 are takenover into phases L2, L3 and L4.55