UMG 508Possible errorsNo connection todevice.The device does notwork despite takingthe above measures.CauseRS485:- Wrong device address.- Different bus speeds- Wrong protocol.- Termination is missing.Ethernet:- IP address is wrongDevice is defective.RemedySet device address.Check and correct the speed(baudrate)Select protocol.Connect bus with terminating resistor(120 Ohm).Set IP address on the device.Send the device to the manufacturer tocheck with an exact description of theerror.83