<strong>ControlMaster</strong> CM10, CM30 and CM50Universal process controllers 1 /8, 1 /4 and 1 /2 DIN6 Basic Level…Basic / …Loop 1 Setpo<strong>in</strong>tsRamp ModeThe ramp<strong>in</strong>g setpo<strong>in</strong>t facility can beused <strong>to</strong> prevent a large disturbance <strong>to</strong><strong>the</strong> control output when <strong>the</strong> setpo<strong>in</strong>tvalue is changed. The rate set applies <strong>to</strong>both <strong>the</strong> local and <strong>the</strong> remote setpo<strong>in</strong>ts.PV3002001000Displayed local setpo<strong>in</strong>t valueActual (ramp<strong>in</strong>g) setpo<strong>in</strong>t value used byPID algorithm*1 HourTime*Example: Ramp Rate = 200 Increments/hrRamp RateLoop 1 ControlOn/Off HysteresisSets <strong>the</strong> ramp rate required <strong>in</strong> eng<strong>in</strong>eer<strong>in</strong>g units / hour.Note. Applicable only if Ramp Mode is On.Sets <strong>the</strong> hysteresis value <strong>in</strong> eng<strong>in</strong>eer<strong>in</strong>g units.PVONOFFReverse Act<strong>in</strong>g Control OutputSetpo<strong>in</strong>tHysteresisValueNote. Applicable only if Control Type is On/Off – see page 55.PVONOFFDirect Act<strong>in</strong>g Control OutputHysteresisValueSetpo<strong>in</strong>t28 IM/CM/S–EN Rev. C