<strong>ControlMaster</strong> CM10, CM30 and CM50Universal process controllers 1 /8, 1 /4 and 1 /2 DIN7 Advanced Level7.3 Input/OutputMenuInput/OutputEnables analog and digital <strong>in</strong>puts / outputs and relays <strong>to</strong> be configured.Analog InputsAnalog Input 1 (4)*Input TypeDigital Volt FreeFreq. InputPulse InputInput types comprise: Millivolts, Milliamps, Volts, Resistance (Ohms), RTD, Thermocouple, Digitalvolt-free, 24V Digital, Freq. Input, Pulse Input.Additional Input Type comments:Acts as a digital <strong>in</strong>put.Sets <strong>the</strong> maximum frequency and equivalent flow rate <strong>in</strong> <strong>the</strong> eng<strong>in</strong>eer<strong>in</strong>g range 0 <strong>to</strong>6000 Hz. (A frequency of up <strong>to</strong> 6 KHz can be used <strong>to</strong> create an analog value.)This parameter counts pulses and is recommended only for use with electromagneticflowmeters.*Analog Inputs 2 <strong>to</strong> 4: Freq Input, Pulse Input and Resistance not available. A Thermocouple <strong>in</strong>put type can be set only if <strong>the</strong> first <strong>in</strong>put is set <strong>to</strong>Thermocouple.IM/CM/S–EN Rev. C 43