1.4. Determining the aerodynamic free opening area in accordance with<strong>EN</strong> <strong>12101</strong>- 2, Annex B<strong>EN</strong> <strong>12101</strong>-2 requires the specification of the aerodynamic free opening area for smoke extraction from the buildingfor each NSHEV in the roof or facade.The aerodynamic free area A ais calculated by multiplying the clear geometric area of the NSHEV with the coefficien<strong>to</strong>f discharge. The coefficient of discharge Cv (with side wind influence) or Cv0 (without side wind influence)is determined by the notified test centre while testing the NSHEV.1.5. Summary: Basic requirements for <strong>D+H</strong> Euro-SHEVsIn summary, the following are the basic requirements for a <strong>D+H</strong> NSHEV in accordance with <strong>EN</strong> <strong>12101</strong>-2:• Drive and window are a single unit• No replacement with non-<strong>D+H</strong> products• Opening time ≤ 60 seconds• Only tested and certified components are usedIf an NSHEV deviates from the values given in the test and certification reports, the certificate becomes invalid.16Section A