Smoke ventilation according to EN 12101-2 - D+H Mechatronic

Smoke ventilation according to EN 12101-2 - D+H Mechatronic

Smoke ventilation according to EN 12101-2 - D+H Mechatronic

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

2.3.2. dEtErMInInG tHE WIdtH/HEIGHt rAtIo of A cASEMEntthe width-height ratio is calculated from the ratio of clear width and clear height:W/H = clear width (rlB): clear height (rlH)W/H = (1200 - 60) : (1600 – 60)W/H = 1 140 : 1 540W/H = 0.74 → W/H < 1.002.3.3. dEtErMInInG tHE oPEnInG AnGlEthe opening angle is read off the following graph as a function of the stroke and the height. the values displayedon this graph are based on a simple sine trigonometric function. the graph is universally applicable across allsystems:Ratio of the opening angle <strong>to</strong> the height dependent on the strokeSash height Fh [mm]Stroke 800Opening angle [DEG]Stroke 300Stroke 1100Stroke 400Stroke 1200Stroke 500Stroke 1300Stroke 600 Stroke 700 Stroke 800 Stroke 900Stroke 1400Stroke 1000In this sample calculation, an opening angle of 37° is calculated at a vent height of 1,600 mm and a stroke ofTeil A1,000 mm.2.3.4. dEtErMInInG tHE coEffIcIEnt of dIScHArGE cV0using the width-height ratio determined under 2.3.2., the coefficient of discharge cv0 required for the nextcalculation can now be read off the corresponding table for the system:Openingasinwardsbot<strong>to</strong>m/<strong>to</strong>phungFrame cleardimensions overlapWWWWOpening angle°At a width-height ratio of 0.74 and an opening angle of 35°, the coefficient of discharge cv0 is 0.40. As theopening angle of 37° calculated in 2.3.3. and the associated cv0 value are not yet reached, the next lowestSection B37

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!