■ either acceptance of a failure rategreater than that already taken as anhypothesis,■ or addition of arresters to theinstallation to ensure the latter is notstressed beyond this level.For high and extra high voltages, theinsulation coordination procedure is thesame, but equipment insulation isgenerally qualified by its switchingimpulse and lightning impulsewithstands.highest voltage standardised short standardised withstandfor equipment duration withstand voltage voltages to lightningUm at power frequency impulseskV rms kV rms kV rms3.6 10 20/407.2 20 40/6012 28 60/75/9517.5 38 75/9524 50 95/125/14536 70 145/17052 95 25072.5 140 325123 (185)/230 450/550145 (185)/230/275 (450)/550/650170 (230)/275/325 (550)/650/750245 (275)/(325)/360/395/460 (650)/(750)/850/950/1050fig. 28: standardised insulation levels for root mean square voltage networks between 1 and245 kV (there is a similar table for voltages greater than 245 kV).rated withstand voltage at short duration to lightningkV power frequency impulsesrated withstand voltage 74 108 141to lightning impulsesequivalence factor 1.06 1.06slow front ➔ fastrated withstand voltage 28 32 42 61to an overvoltage at shortduration power frequencyequivalence factor 0.6 0.6slow front ➔ 50 Hzspecified withstand voltagewithstand voltage 28 32 70 102 141altitude correction 1.13 1.13 1.13dispersion factor 1.15 1.15 1.05 1.05 1.05coordination withstand voltage 24 28 59 86 119*(case of equipment subjectedto atmospheric pressures)overvoltages in operationconventional representative short duration 250-2,500 µs impulse 1.2-50 µs impulseimpulse shape 50 Hz power frequency (1 mn) 2 % arcingconventional representative 24 28 59 86amplitude (kV) (2.6 p.U.) (3.86 p.U)overvoltage categories phase / phase to phase / phase to phase / frame andframe phase frame phase phase to phasetemporary slow front fast frontat power frequency (switching) (lightning)*: this value comes from the followingcriteria:- arrester protection level: 80 kW- arrester/equipment clearance: 8 m- safety factor: 1.05Calculation example:for a slow front coordination withstand voltage of 59 kV■ slow front specified withstand voltage = 59 kV x 1.05 x 1.13 = 70 kV■ equivalent rated withstand voltage at standard short term frequency = 70 kV x 0.6 = 42 kV■ equivalent rated withstand voltage to lightning impulses = 70 kV x 1.06 = 74 kV.fig. 29: example of an insulation coordination study for a 24 kV network, with external insulation equipment (taken and adapted from the draftrevisionof IEC 71).Cahier Technique Merlin Gerin n° 151 / p.19

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!