Model YLAA Air-Cooled Scroll Compressor Liquid Chillers Style B
Model YLAA Air-Cooled Scroll Compressor Liquid Chillers ... - DCES
Model YLAA Air-Cooled Scroll Compressor Liquid Chillers ... - DCES
- No tags were found...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Dimensions – Four Fan UnitsPHFPDR1R2W C1 C2L<strong>YLAA</strong> <strong>Model</strong>L(length)W(width)H(height)F P D C1 C2 R2 R1<strong>YLAA</strong>0070ZE 116.0 88.3 95.3 89.6 43.9 13.4 19.0 84.5 68.3 23.0<strong>YLAA</strong>0080ZE 116.0 88.3 95.3 89.6 43.9 15.0 18.6 85.0 68.3 23.0<strong>YLAA</strong>0090ZE 116.0 88.3 95.3 89.6 43.9 16.3 19.6 83.0 68.3 23.0NOTE:Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliableoperation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflowpatterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safetycutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit isno higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top– no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.32 jOHNSON CONTROLS