RE-2Y(St)CH-fl<br />
RE-2X(St)CH-fl<br />
EN 50288-7<br />
Multi-Pair, Braid+Metallic Screened, Instrumentation Cables300 V-500 V<br />
KLAS KABLO RE-2Y(St)CH-fl<br />
APPLICATION<br />
These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial premises, power<br />
plants, natural gas and petroleum industries, etc. Direct connection is not permitted under ambient with a low impedance sources. Cables with blue sheaths are suitable for<br />
security system applications. Furthermore, these cables can directly be buried in the soil. They are suitable in dry and wet indoor and outdoor installations.<br />
CONSTRUCTION<br />
GENERAL FEATURES<br />
1-Inner Conductor<br />
2-Insulation<br />
3-Communication<br />
Core<br />
4-Lay-Up<br />
5-Overall Screening<br />
6-Outer sheath<br />
• Electrolytic stranded annealed copper wire (IEC 60228, Class 2)<br />
2Y • PE (EN 50290-2-23)<br />
2X XLPE (EN 50290-2-29)<br />
• 0,50 mm² (7x0,30 mm) tinned or annealed standed copper, PE or XLPE insulated orange core.<br />
(More than one double or triple cables)<br />
• Screened pair cores are strand communication core with together twisted layers. Fixed with PES tape.<br />
(St)C • %100 Coverage AL-PES tape and tinned copper wire braid with screened.<br />
H • HFFR sheath (EN 50290-2-27), RAL 9005 Black, RAL 5015 Blue or RAL 7001 Grey<br />
Flame Retardent<br />
(For a single cable)<br />
Flame Retardent<br />
(For a Bunch Cable)<br />
Determination of Flame Particles<br />
Test (Test of determination of<br />
flaming droplets)<br />
Halogen Acid Gas Test<br />
> IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2<br />
> IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24<br />
> IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3<br />
> IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1<br />
Asidic (Corrosive)<br />
Gas Test<br />
Smoke Density Test > IEC 61034-2, EN 61034-2,<br />
VDE 0482-1034-2<br />
Oil Resistance > ICEA S-82-552<br />
UV Resistance<br />
> IEC 60754-2, EN 50267-2-2,<br />
VDE 0482-267-2-2<br />
> Only valid for Black sheath cables.<br />
TECHNICAL PROPERTIESTIES<br />
PE (2Y)<br />
XLPE (2X)<br />
Fixed<br />
Flexible<br />
Fixed<br />
Flexible<br />
Temperature Range (°C) -30 °C …. +70 °C<br />
-5 °C …. +50 °C<br />
-30 °C …. +90 °C<br />
-5 °C …. +50 °C<br />
Min. Bending Radius (mm)<br />
7,5xD<br />
ELECTRICAL CHARACTERISTICS<br />
300 V 500 V<br />
Cross Section (mm²)<br />
0,5 0,75 1,0 1,3 1,5 2,5 0,5 0,75 1,0 1,3 1,5 2,5<br />
Conductor DC Resistance (Ω/km)<br />
36,8 25,0 18,5 14,2 12,3 7,56 36,8 25,0 18,5 14,2 12,3 7,56<br />
Insulation Resistance (M.Ω.km) PE ve XLPE : ≥ 5000<br />
PE ve XLPE : ≥ 5000<br />
Capacity (800 MHz) (pF/m)<br />
Capacity Unbalance<br />
PE ve XLPE : < 150<br />
PE for materials : 500 pF/ 500 m<br />
PE ve XLPE : < 150<br />
PE for materials : 500 pF/ 500 m<br />
L/R Raito (max.) (μH/Ω)<br />
25 25 25 40 40 60 25 25 25 40 40 60<br />
Operating Voltage<br />
Max. 300 V<br />
Max. 500 V<br />
Test Voltage (V ac) 1 minutes<br />
1000<br />
2000<br />
HFFR SHEATHED CABLES<br />
6.47<br />
ALTERNATIVE CABLE STRUCTURES<br />
Insulation<br />
Screen Features<br />
H – Halogen Free<br />
C – Braid screen, CuB – Copper tape screened<br />
CORE COLOURS 300 V 500 V<br />