RE-2X(St)CH-CI FE-180 PH120<br />

EN 50288-7<br />

Multi-Pair, Braid+Metallic Screen, Fire-Resistant Instrumentation Cables<br />

300 V-500 V<br />

KLAS KABLO RE-2X(St)CH-CI FE-180 PH120<br />

APPLICATION<br />

These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial<br />

premises, power plants, natural gas and petroleum industries, etc. Direct connection is not permitted under ambient with a low impedance sources. Cables with blue sheaths<br />

are suitable for security system applications. Furthermore, these cables can directly be buried in the soil. They are suitable in dry and wet indoor and outdoor installations.<br />

CONSTRUCTION<br />

1-Inner conductor<br />

2-Insulation<br />

3-Lay-Up<br />

4-Overall Screen<br />

5-Outer Sheath<br />

2X<br />

(St) C<br />

H<br />

• Electrolytic stranded annealed copper wire (IEC 60228, Class 2)<br />

• Mica tape on the XLPE insulation ( EN 50290-2-29)<br />

• Screened pair cores are twisted in layers. Fixed with PES tape.<br />

• %100 Coverage AL-PES tape ve screened with tinned copper wire braided.<br />

• HFFR Sheath (EN 50290-2-27), RAL 9005 Black, RAL 5015 Blue veya RAL 7001 Grey<br />

GENERAL FEATURES<br />

Flame Retardent<br />

(For a single cable)<br />

Flame Retardent<br />

(For a Bunch Cable )<br />

TECHNICAL PROPERTIES<br />

XLPE (2X)<br />

Fixed<br />

Flexible<br />

Temperature Range (°C) -30 °C …. +90 °C -5 °C …. +50 °C<br />

Min. Bending Radius (mm)<br />

10xD<br />

ELECTRICAL CHARACTERISTICS<br />

300 V 500 V<br />

Cross Section (mm²)<br />

0,5 0,75 1,0 1,3 1,5 2,5 0,5 0,75 1,0 1,3<br />

Conductor DC Resistance (Ω/km)<br />

36,8 25,0 18,5 14,2 12,3 7,56 36,8 25,0 18,5 14,2<br />

Insulation Resistance (M.Ω.km) ≥ 5000<br />

≥ 5000<br />

Capacity (800 MHz) (pF/m)<br />

< 150<br />

< 150<br />

Capacity Unbalance<br />

500 pF/ 500 m<br />

500 pF/ 500 m<br />

L/R Raito (max.) (μH/Ω)<br />

Operating Voltage<br />

Test Voltage (V ac) 1 minutes<br />

> IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2<br />

> IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24<br />

Determination of > IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3<br />

Flame Particles Test<br />

(Test of determination<br />

of flaming droplets)<br />

Halogen Acid<br />

Gas Test<br />

Acidic (Corrosive)<br />

Gas Test<br />

> IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1<br />

> IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2<br />

25<br />

25<br />

V<br />

FE-180<br />

V<br />

PH120<br />

25 40<br />

Max. 300 V<br />

1000<br />

Smoke Density Test > IEC 61034-2, EN 61034-2, VDE 0482-1034-2<br />

Insulation continuity<br />

test (FE-)<br />

Circuit InteGreyty With<br />

Shock (PH)<br />

Oil Resistance<br />

40<br />

60<br />

25<br />

> IEC 60331-21, VDE 472 part 814<br />

> EN 50200, VDE 0482-200<br />

> ICEA S-82-552<br />

25<br />

25 40<br />

Max. 500 V<br />

2000<br />

1,5<br />

12,3<br />

40<br />

2,5<br />

7,56<br />

60<br />

FIRE RESISTANT MICA TAPE<br />

<strong>INSTRUMENTATION</strong> CABLES<br />

6.87<br />

ALTERNATIVE CABLE CONSTRUCTIONS<br />

Insulation<br />

Screen Features<br />

H – Halogen Free,<br />

C – Braid screen, CuB – Copper tape screened<br />

CORE COLOURS 300 V 500 V<br />

www.klaskablo.com