RE-2Y(St)H-fl MC<br />

RE-2X(St)H-fl MC<br />

EN 50288-7<br />

Multi-core, Overall Screen Signalling Cables<br />

300 V-500 V<br />

KLAS KABLO RE-2Y(St)H-fl MC<br />

APPLICATION<br />

These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial<br />

premises, power plants, natural gas and petroleum industries, etc. Direct connection is not permitted under ambient with a low impedance sources. Cables with blue sheaths<br />

are suitable for security system applications. Furthermore, these cables can directly be buried in the soil. They are suitable in dry and wet indoor and outdoor installations.<br />

YAPI<br />

1-Inner conductor<br />

2-Insulation<br />

3-Lay-Up<br />

4-Overall Screen<br />

5-Outer Sheath<br />

2Y<br />

2X<br />

(St)<br />

H<br />

• Electrolytic stranded annealed copper wire (IEC 60228, Class 2)<br />

• PE (EN 50290-2-23)<br />

XLPE (EN 50290-2-29)<br />

• Cores are twisted in layers. Fixed with PES tape.<br />

• %100 Coverage AL-PES tape ve 0,50 mm² (7x0,30 mm) screened with tinned strand drain wire.<br />

• HFFR Sheath (EN 50290-2-27), RAL 9005 Black, RAL 5015 Blue veya RAL 7001 Grey<br />

GENERAL FEATURES<br />

Flame Retardent<br />

(For a single cable)<br />

Flame Retardent<br />

(For a Bunch Cable)<br />

> IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-1-2<br />

> IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24<br />

Determination of > IEC 60332-1-3, EN 60332-1-3, VDE 0482-332-1-3<br />

Flame Particles Test<br />

(Test of determination<br />

of flaming droplets)<br />

Halogen Acid Gas > IEC 60754-1, EN 50267-2-1, VDE 0482-267-2-1<br />

Test<br />

Acidic (Corrosive)<br />

Gas Test<br />

Oil Resistance<br />

UV Resistance<br />

> IEC 60754-2, EN 50267-2-2, VDE 0482-267-2-2<br />

Smoke Density Test > IEC 61034-2, EN 61034-2, VDE 0482-1034-2<br />

> ICEA S-82-552<br />

> Only valid for Black sheath cables..<br />

TECHNICAL PROPERTIES<br />

PE (2Y)<br />

XLPE (2X)<br />

Fixed<br />

Flexible<br />

Fixed<br />

Flexible<br />

Temperature Range (°C) -30 °C …. +70 °C -5 °C …. +50 °C -30 °C …. +90 °C<br />

-5 °C …. +50 °C<br />

Min. Bending Radius (mm)<br />

10xD<br />

ELECTRICAL CHARACTERISTICS<br />

300 V 500 V<br />

Cross Section (mm²)<br />

0,5 0,75 1,0 1,3 1,5 2,5 0,5 0,75 1,0 1,3 1,5<br />

Conductor DC Resistance (Ω/km)<br />

36,8 25,0 18,5 14,2 12,3 7,56 36,8 25,0 18,5 14,2 12,3<br />

Insulation Resistance (M.Ω.km) PE ve XLPE : ≥ 5000<br />

PE ve XLPE : ≥ 5000<br />

Capacity (800 MHz) (pF/m)<br />

Capacity Unbalance<br />

PE ve XLPE : < 150<br />

PE for Materials : 500 pF/ 500 m<br />

PE ve XLPE : < 150<br />

PE for Materials : 500 pF/ 500 m<br />

L/R Raito (max.) (μH/Ω)<br />

25 25 25 40 40 60 25 25 25 40 40<br />

Operating Voltage<br />

Max. 300 V<br />

Max. 500 V<br />

Test Voltage (V ac) 1 minutes<br />

1000<br />

2000<br />

2,5<br />

7,56<br />

60<br />

HFFR SHEATHED<br />

<strong>INSTRUMENTATION</strong> CABLES<br />

6.61<br />

ALTERNATIVE CABLE CONSTRUCTIONS<br />

Insulation<br />

Screen Features<br />

H – Halogen Free<br />

C – Braid screen, (St)C – AL foil+Braid screen, CuB – Copper tape screened<br />

IDENTIFICATION OF CORE COLOURS<br />

According to HD 402 S2; White, Red, Black, Yellow, Blue, Green, Orange, Grey, Brown, Turquoise, Purple, Pink<br />

Or White number onto Black core Besides, the customer request might be included, provided that informed in advance.<br />