<strong>Pressure</strong> switches<br />
Accessories<br />
61<br />
Accessories for EX 041 series<br />
for intrinsically safe control circuits with short-circuit<br />
and line break monitoring<br />
EX 041<br />
· 1-channel<br />
· 1 failsafe relay output<br />
according to DIN VDE 0660 Part 209<br />
(BIA certificate no. 940 64)<br />
· Control circuit EEx-ia IIC<br />
· 1 progressive output with 1 normally open<br />
contact<br />
· 1 passive electronic output, error message<br />
Application<br />
Suitable for all safety-engineered pressure monitors/pressure<br />
limiters, with microswitches and<br />
resistor combination<br />
ZF 576 ZF 574 ZF 577 ZF 575,<br />
FD series<br />
Technical data<br />
Nominal voltage 230V, 48 Hz…62 Hz<br />
Power consumption 3 W<br />
Input (intrinsically safe) Terminals 10+, 12–<br />
No-load voltage/short-circuit current<br />
approx. 8.4 VDC/approx. 11.7 mA<br />
Switching point<br />
Relay dropped out J < 2.1 mA and J > 5.9 mA<br />
Relay picked up 3.2 mA < J < 5mA<br />
Line resistance<br />
< 50 ohm. Cable capacitances and inductance<br />
must be taken into account in the Ex area.<br />
PTB approval PTB 00 ATEX 2043<br />
Explosion protection, category EEx-ia<br />
Outputs (not intrinsically safe)<br />
Output I: (failsafe)<br />
Relay terminals 13, 14<br />
Output II: (not failsafe)<br />
Relay terminals 15, 21<br />
Contact load<br />
AC: 250V/1 A/cos. > 0.7<br />
DC: 24V/1 A resistive load<br />
Output III<br />
Error message (not failsafe)<br />
Electronic output, passive, terminals 16+, 17–<br />
Nominal voltage DC 10 V…30 V<br />
Nominal current < 7 mA, short-circuit-proof<br />
Switching frequency 5 Hz<br />
Ambient temperature –20°C…+60°C<br />
Installation Standard rail 35 mm.<br />
Dimensions<br />
40 x 115 x 93 (W x H x D).<br />
The type EX 041 isolating amplifier is used for the transmission of intrinsically safe control commands<br />
(e.g. from pressure switches) to non-intrinsically safe active circuits. In the event of short-circuit<br />
or line break in the control circuit, the isolating amplifier switches to the safe side (see<br />
“Direction of action” table). It also reacts to the safe side (output relay drops out) if internal component<br />
failures and resultant errors occur.<br />
Output I Relay output failsafe according to VDE 0660, Part 209, terminals separately led to the<br />
outside for series connected protective interlock circuit, for example.<br />
Output II Progressive output with relay stage (not failsafe).<br />
Output III Alarm output potential-free (not failsafe).<br />
Important note<br />
The type EX 041 isolating amplifier can only be used together with pressure switches with resistor<br />
combination (additional function ZF 576, ZF 577…, see also “Application” above).<br />
Direction of action<br />
Control circuit Output relay Status indicator Electronic<br />
I and II yellow red output III<br />
Switching contact closed picked up on off blocked<br />
Switching contact open dropped out off off blocked<br />
Line break or short-circuit dropped out off on switched<br />
in the input circuit<br />
through<br />
Contact welding dropped out off on switched<br />
Output I<br />
through<br />
Type designation<br />
Type Supply voltage Power consumption<br />
EX 041 230 V, 48…62 Hz 3 W<br />
s