<strong>Pressure</strong> switches<br />

Accessories<br />

61<br />

Accessories for EX 041 series<br />

for intrinsically safe control circuits with short-circuit<br />

and line break monitoring<br />

EX 041<br />

· 1-channel<br />

· 1 failsafe relay output<br />

according to DIN VDE 0660 Part 209<br />

(BIA certificate no. 940 64)<br />

· Control circuit EEx-ia IIC<br />

· 1 progressive output with 1 normally open<br />

contact<br />

· 1 passive electronic output, error message<br />

Application<br />

Suitable for all safety-engineered pressure monitors/pressure<br />

limiters, with microswitches and<br />

resistor combination<br />

ZF 576 ZF 574 ZF 577 ZF 575,<br />

FD series<br />

Technical data<br />

Nominal voltage 230V, 48 Hz…62 Hz<br />

Power consumption 3 W<br />

Input (intrinsically safe) Terminals 10+, 12–<br />

No-load voltage/short-circuit current<br />

approx. 8.4 VDC/approx. 11.7 mA<br />

Switching point<br />

Relay dropped out J < 2.1 mA and J > 5.9 mA<br />

Relay picked up 3.2 mA < J < 5mA<br />

Line resistance<br />

< 50 ohm. Cable capacitances and inductance<br />

must be taken into account in the Ex area.<br />

PTB approval PTB 00 ATEX 2043<br />

Explosion protection, category EEx-ia<br />

Outputs (not intrinsically safe)<br />

Output I: (failsafe)<br />

Relay terminals 13, 14<br />

Output II: (not failsafe)<br />

Relay terminals 15, 21<br />

Contact load<br />

AC: 250V/1 A/cos. > 0.7<br />

DC: 24V/1 A resistive load<br />

Output III<br />

Error message (not failsafe)<br />

Electronic output, passive, terminals 16+, 17–<br />

Nominal voltage DC 10 V…30 V<br />

Nominal current < 7 mA, short-circuit-proof<br />

Switching frequency 5 Hz<br />

Ambient temperature –20°C…+60°C<br />

Installation Standard rail 35 mm.<br />

Dimensions<br />

40 x 115 x 93 (W x H x D).<br />

The type EX 041 isolating amplifier is used for the transmission of intrinsically safe control commands<br />

(e.g. from pressure switches) to non-intrinsically safe active circuits. In the event of short-circuit<br />

or line break in the control circuit, the isolating amplifier switches to the safe side (see<br />

“Direction of action” table). It also reacts to the safe side (output relay drops out) if internal component<br />

failures and resultant errors occur.<br />

Output I Relay output failsafe according to VDE 0660, Part 209, terminals separately led to the<br />

outside for series connected protective interlock circuit, for example.<br />

Output II Progressive output with relay stage (not failsafe).<br />

Output III Alarm output potential-free (not failsafe).<br />

Important note<br />

The type EX 041 isolating amplifier can only be used together with pressure switches with resistor<br />

combination (additional function ZF 576, ZF 577…, see also “Application” above).<br />

Direction of action<br />

Control circuit Output relay Status indicator Electronic<br />

I and II yellow red output III<br />

Switching contact closed picked up on off blocked<br />

Switching contact open dropped out off off blocked<br />

Line break or short-circuit dropped out off on switched<br />

in the input circuit<br />

through<br />

Contact welding dropped out off on switched<br />

Output I<br />

through<br />

Type designation<br />

Type Supply voltage Power consumption<br />

EX 041 230 V, 48…62 Hz 3 W<br />

s