7-2. Freeze Prevention<br />
● This function prevents freezing of the indoor heat exchange coil.<br />
● When the compressor has been running for 10 minutes or more and the temperature of the indoor heat<br />
exchange coil falls below –1°C, the control circuit stops the compressor for at least 6 minutes. The compressor<br />
does not start again until the temperature rises above 8°C or 6 minutes has elapsed.<br />
T+1 °C<br />
Set temp. T °C<br />
Indoor heat exch.<br />
coil temp.<br />
–1 °C<br />
Compressor<br />
Indoor fan<br />
Room temp.<br />
More than<br />
10 minutes<br />
ON OFF ON ON OFF ON<br />
Set speed<br />
6 minutes<br />
21<br />
More than<br />
10 minutes<br />
Thermo. OFF<br />
Thermo. ON<br />
More than<br />
6 minutes<br />
Set speed