Table E-1 (Continued). Unit electrical data for standard efficiency at all ambient operation<br />
Unit Wiring Motor Data<br />
# of Max. Fuse, HACR Rec. Time Compressor (Each) Fans (Each)<br />
Unit Rated Power MCA (3) Breaker or MOP (11) Delay or RDE (4) RLA (5) XLRA (8) YLRA (8) Qty. Control<br />
Size Voltage Conns (1) Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 Qty Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 Ckt 1/Ckt 2 kW FLA kW (7)<br />
200/60/3 1 NA<br />
200/60/3 2 1124/947 1200/1200 1200/1200 4 459/459/386/386 NA 821/821/701/701 14/12 1.5 6.5 1.59<br />
230/60/3 1 NA<br />
230/60/3 2 989/834 1200/1000 1200/1000 4 399/399/336/336 NA 691/691/571/571 14/12 1.5 6.5 1.59<br />
RTAC 380/60/3 1 NA<br />
450 380/60/3 2 594/499 800/700 700/600 4 242/242/203/203 1306/1306/1060/1060 424/424/345/345 14/12 1.5 3.5 1.59<br />
460/60/3 1 859 1000 1000 4 200-200-168-168 1065-1065-878-878 346-346-285-285 26 1.5 2.8 1.59<br />
460/60/3 2 490/412 600/500 600/500 4 200/200/168/168 1065/1065/878/878 346/346/285/285 14/12 1.5 2.8 1.59<br />
575/60/3 1 688 800 800 4 160-160-134-134 853-853-705-705 277-277-229-229 26 1.5 2.3 1.59<br />
575/60/3 2 393/330 500/450 450/400 4 160/160/134/134 853/853/705/705 277/277/229/229 14/12 1.5 2.3 1.59<br />
200/60/3 1 NA<br />
200/60/3 2 1124/1124 1200/1200 1200/1200 4 459/459/459/459 NA 821/821/821/821 14/14 1.5 6.5 1.59<br />
230/60/3 1 NA<br />
230/60/3 2 989/989 1200/1200 1200/1200 4 399/399/399/399 NA 691/691/691/691 14/14 1.5 6.5 1.59<br />
RTAC 380/60/3 1 NA<br />
500 380/60/3 2 594/594 800/800 700/700 4 242/242/242/242 1306/1306/1306/1306 424/424/424/424 14/14 1.5 3.5 1.59<br />
460/60/3 1 929 1000 100 4 200-200-200-200 1065-1065-1065-1065 346-346-346-346 28 1.5 2.8 1.59<br />
460/60/3 2 490/490 600/600 600/600 4 200/200/200/200 1065/1065/1065/1065 346/346/346/346 14/14 1.5 2.8 1.59<br />
575/60/3 1 745 800 800 4 160-160-160-160 853-853-853-853 277-277-277-277 28 1.5 2.3 1.59<br />
Notes:<br />
575/60/3 2 393/393 500/500 450/450 4 160/160/160/160 853/853/853/853 277/277/277/277 14/14 1.5 2.3 1.59<br />
1. As standard, all units have single point power connection. Optional dual point power connections are available.<br />
2. Max Fuse or HACR type breaker = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA per NEC 440-22.<br />
Use FLA per circuit, NOT FLA for the entire unit).<br />
3. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of the second compressor RLA plus the sum of the condenser fans FLAs per NEC 440-33.<br />
4. RECOMMENDED TIME DELAY OR DUAL ELEMENT (RDE) FUSE SIZE: 150 percent of the largest compressor RLA plus 100 percent of the second compressor RLA and the sum of the condenser<br />
fan FLAs.<br />
5. RLA - Rated Load Amps - rated in accordance with UL Standard 1995.<br />
6. Local codes may take precedence.<br />
7. Control kW includes operational controls only. Does not include evaporator heaters.<br />
8. XLRA - Locked Rotor Amps - based on full winding (x-line) start units. YLRA for wye-delta starters is ~1/3 of LRA of x-line units.<br />
9. VOLTAGE UTILIZATION RANGE:<br />
Rated Voltage Utilization Range<br />
200/60/3 180-220<br />
230/60/3 208-254<br />
380/60/3 342-418<br />
460/60/3 414-506<br />
575/60/3 516-633<br />
400/50/3 360-440<br />
10. A separate 115/60/1, 20 amp or 220/50/1, 15 amp customer provided power connection is needed to power the evaporator heaters (1640 watts).<br />
11. If factory circuit breakers are supplied with the chiller, then these values represent Maximum Overcurrent Protection (MOP).<br />
12. When the circuit breaker option is ordered, two circuit breakers will be provided (one per circuit) for both single and dual point power.<br />
13. Motor kW is for standard fans. Low noise fans at 50 Hz are rated at 1.1 kW/fan.<br />
40<br />
Electrical Data<br />
and Connection<br />
RLC-PRC006-EN