8<br />

VARIODYN D1 Digital Output Module (DOM)<br />

¬[B^§/33/FT,<br />

583361.22.ES Digital Output Module DOM4-8<br />

1<br />

Features<br />

• Permitted as per EN 54-16<br />

• Compliant with IEC 60849<br />

• All functions of an alarm and evacuation system in<br />

a 19"-module (DOM)<br />

• Networkable via Ethernet<br />

• Permanent monitoring of all functionally-relevant<br />

system parts<br />

• Automatic and dynamic switching onto redundant<br />

spare amplifier<br />

• Automatic loudspeaker regulation (ALR) also<br />

during announcements<br />

• Remote monitoring and configuration via network<br />

24 V DC power supply<br />

• Spur technology and/or loop technology in "VARI-<br />

ODYN D1 Loop Technology"<br />

• Connection to a NTP server via Ethernet is<br />

possible<br />

www.hls-austria.com<br />

Approval: VdS<br />

Part of EN 54-16 approval 0786-CPD-20997<br />

DOM is the central control element of VARIODYN D1. It has interfaces to all input/output<br />

assemblies, administers and monitors the loudspeaker circuits. For voice alarm systems as<br />

per DIN VDE 0833-4. Any complex system configuration can be implemented through the<br />

networking of multiple DOMs via the Ethernet. All power amplifiers are permanently monitored.<br />

In case a power amplifier is faulty, it can be replaced dynamically by a spare amplifier.<br />

The switchover is done automatically via the DOM. Loudspeaker cables are continually<br />

monitored for short-circuit, short-to-ground, interruption and impedance vari ation. Faulty<br />

loudspeaker areas are separated without reaction. A DOM contains storage capacity for<br />

preset announcements, which can be used for alarm texts and signals (escape alarm,<br />

caution signal) and warning signals (gongs). The volume of each source and ampli fier<br />

channel can be regulated. Other filters, e.g., parametric equalizers, high and low pass filters<br />

and delays, are also available. All disturbances are recognized within a few seconds in<br />

compliance with standards, displayed and logged. For special applications, e.g., tunnels,<br />

delays of up to 9.9 seconds can be programmed. The control unit DOM4-8 is equipped<br />

with 4 independent amplifier channels in order to operate 8 loudspeaker areas or 4 loudspeaker<br />

circuits in VARIODYN D1 Loop Technology. There is also the option of mixing loop<br />

and spur technology with a DOM.<br />

Technical Data<br />

Audio output:<br />

Output type symmetrically<br />

Nominal level 0 dBu<br />

max. Outputlevel < 6 dBu<br />

Transmission range 20 ... 20000 Hz<br />

Harmonic distortion at nominal < 0.03 % @ 1 kHz<br />

level<br />

Signal/Noise ratio > 70 dB / 75 dB (A)<br />

Output impedance<br />

Sensor Input (AVC):<br />

> 5 kΩ, < 500 pF<br />

Input type symmetrically<br />

Nominal level -51 dBu<br />

Nominal level for emergency telephone<br />

station<br />

0 dBu<br />

Transmission range 100 ... 8000 Hz<br />

Harmonic distortion at nominal < 0.02 % @ 1 kHz<br />

level<br />

Signal/Noise ratio > 60 dB / 65 dB (A)<br />

Load impedance typ. 200 Ω<br />

Common technical data:<br />

Rated voltage 90 .. 264 V AC<br />

Rated frequency 47 ... 440 Hz<br />

Emergency power supply 24<br />

Power consumption 40 / 70 W (@230 V, w/o / with 4 x DAL)<br />

Contact load relay 100 V DC / 1 A<br />

Ambient temperature -5 °C ... 55 °C<br />

Air humidity 15 % ... 90 % (non condensing)<br />

Weight approx. 6.8 kg<br />

Dimensions W: 483 mm H: 44 mm D: 345 mm (1 HE, 19")<br />

Accessories<br />

583451.21 Cable for rear panel of DOM4-8 cabinet<br />

583486 Cat 5 patch cable, 1 m yellow (Ethernet)<br />

583487 Cat 5 patch cable, 2 m yellow (Ethernet)<br />

583488 Cat 5 patch cable, 3 m yellow (Ethernet)<br />

583496 End of Line Module (EOL)<br />

581316 P4 Microphone for AVR<br />

583703 Mounting Kit 1<br />

583342 Loop Isolator Module