18<br />
VARIODYN D1 Call Stations<br />
Fire Control PA Panel<br />
¬[B$§/32)<br />
583303.21 Digital Fire Control PA Panel DCSF12<br />
1<br />
www.hls-austria.com<br />
196<br />
174<br />
134<br />
116<br />
Features<br />
• Manual microphone with built-in loudspeaker and<br />
acoustic microphone monitoring<br />
• Permanent monitoring of the line to the following<br />
interface module<br />
• 24-bit AD/DA converter<br />
• 12 freely configurable keys<br />
40<br />
Approval: VdS<br />
Part of EN 54-16 approval 0786-CPD-20997<br />
The Digital Fire Control PA Panel DCSF12 allows for the selection of loudspeaker circuits,<br />
transmission of voice announcements as well as of various tones and alarms. The communication<br />
unit is connected to a free DAL-bus (Digital Audio Link) on the DOMs (Digital<br />
Output Modules) via a standard CAT 5 cable. All control signals as well as all audio signals<br />
are transmitted digitally. The communication unit has 12 freely configurable keys, 13 LEDs<br />
and a manual microphone with a built-in loudspeaker. Up to four digital communication<br />
units can be connected to one DOM. Every digital communication unit can simultaneously<br />
produce and receive different voice signal through-connections and control signals within<br />
the system. A digital communication unit can be relocated by up to 300 m via a Cat 5 cable<br />
(expansion up to 2,000 m possible using fiber optic cabling) and can be expanded with up<br />
to six DKM18 digital key modules; this increases the total number of available keys and<br />
LEDs to 120 per communication unit.<br />
The inaudible monitoring frequencies sent by the loudspeaker are continuously picked up<br />
by the microphone. Any interruption will lead to an error message.<br />
Technical Data<br />
Microphone Elektret, cardoid characteristic<br />
Transmission range 200 ... 12500 Hz<br />
Loudspeaker 1 W<br />
Sample rate 48 kHz<br />
AD/DA converter 24 Bit<br />
Current consumption < 150 mA<br />
Ambient temperature -5 °C ... 55 °C<br />
Air humidity 15 % ... 90 %<br />
Color black, similar to RAL 9005 (side frames)<br />
grey, similar to RAL 7037 (middle body)<br />
Weight approx. 1.6 kg<br />
Dimensions W: 134 mm H: 40 mm D: 196 mm<br />
A transparent keyboard cover is available in order to provide protection against unintentional<br />
keystrokes. This way, pressing keys is only possible with the cover open. Each cover can protect<br />
three horizontally arranged keys.<br />
A 3 m long Cat 5 cable for connection of the digital communication unit to a wall jack is included<br />
with delivery.<br />
Accessories<br />
583306.21 Digital Key Module DKM18<br />
583311 Keyboard Cover for VARIODYN D1 DCS Communication Unit<br />
583312 Installation Kit for Communication Unit DCS onto table VARIODYN D1, 19 inch<br />
583316.21 Fiber Optics Conversion for OIM Control Unit VARIODYN D1<br />
583317.21 Fiber Optics for Digital Communication Units DCS VARIODYN D1<br />
583315.02 Power Supply for Fiber Optics Converter DCS O VARIODYN D1<br />
583307 Wall Jack for VARIODYN D1 DCS Communication Unit<br />
583300.ES Adhesive Label for DCS "ESSER by <strong>Honeywell</strong>"<br />
583318 Replacement Keycaps (package of 12 pieces)<br />
584961 Housing for one FW - Callstation DCSF<br />
584962 Housing for two FW - Callstations DCSF