Section: Power Options \ 3% Dynamic Braking Options<br />

3% Dynamic Braking Options<br />

3% Duty cycle resistors are rated for a 3% duty cycle at 100 second intervals.<br />

Table 22: 240 Volt 3% Dynamic Braking Options<br />

Normal Duty HP<br />

Heavy Duty HP<br />

Catalog Code<br />

GA80U . .<br />

Resistor<br />

Part Number Quantity Ohms (each) Watts (each)<br />

1 0.75 2004. . . R7506 1 300 150<br />

1.5 1 2006. . . R7505 1 200 150<br />

2 1.5 2008. . . R7504 1 100 150<br />

3 2 2010. . . R7504 1 100 150<br />

4 3 2012. . . R7510 1 62 150<br />

5 4 2018. . . R7510 1 62 150<br />

7.5 5 2021. . . R7510 2 62 150<br />

These resistors offer approximately 100% peak braking power.<br />

Table 23: 480 Volt 3% Dynamic Braking Options<br />

Normal Duty HP<br />

Heavy Duty HP<br />

Catalog Code<br />

GA80U . .<br />

Resistor<br />

Part Number Quantity Ohms (each) Watts (each)<br />

1 0.75 4002. . . R7508 1 750 150<br />

2 1.5 4004. . . R7507 1 400 150<br />

3 2 4005. . . R7505 1 200 150<br />

4 3 4007. . . R7505 1 200 150<br />

5 4 4009. . . R7505 1 200 150<br />

7.5 5 4012. . . R7504 1 100 150<br />

These resistors offer approximately 100% peak braking power.<br />