Section: Drive Short Circuit Protection \<br />

Table 45: 480 Volt Model Protection Ratings<br />

Semiconductor Fuses<br />

EATON/Bussmann 1<br />

Class CC, J, or T Fuses 2<br />

MCCBs (Molded Case Circuit Breakers)<br />

or Class RK Fuses 3<br />

Drive<br />

Catalog<br />

Code<br />

GA80U . .<br />

Part<br />

Number<br />

Maximum<br />

SCCR<br />

(Fuse-Drive<br />

Combination)<br />

Maximum Fuse<br />

Size (Amps)<br />

Maximum SCCR<br />

(Fuse-Drive<br />

Combination)<br />

Maximum<br />

MCCB Size<br />

(Amps)<br />

Maximum<br />

RK1 or RK5<br />

Fuse Size<br />

(Amps)<br />

Minimum<br />

Enclosure<br />

Volume<br />

(in3)<br />

Maximum<br />

SCCR<br />

(MCCB-Drive<br />

or<br />

RK Fuse-Drive<br />

Combination)<br />

4002. . .<br />

FWH-40B<br />

or FWH-50B<br />

100 kA 3.5 100 kA 15 3.5 4,195 100 kA<br />

4004. . . FWH-50B 100 kA 7 100 kA 15 7 4,195 100 kA<br />

4005. . . FWH-50B 100 kA 9 100 kA 15 9 4,195 100 kA<br />

4007. . . FWH-60B 100 kA 12 100 kA 15 12 4,195 100 kA<br />

4009. . . FWH-60B 100 kA 15 100 kA 15 15 4,195 100 kA<br />

4012. . . FWH-60B 100 kA 20 100 kA 20 20 4,195 100 kA<br />

4018. . . FWH-80B 100 kA 30 100 kA 35 30 4,195 100 kA<br />

4023. . . FWH-90B 100 kA 40 100 kA 45 40 4,195 100 kA<br />

4031. . .<br />

FWH-125B<br />

or FWH-150B<br />

100 kA 50 100 kA 60 50 4,195 100 kA<br />

4038. . . FWH-200B 100 kA 60 100 kA 75 60 4,195 100 kA<br />

4044. . . FWH-200B 100 kA 70 100 kA 80 70 4,195 100 kA<br />

4060. . . FWH-225A 100 kA 100 100 kA 110 100 4,195 100 kA<br />

4075. . . FWH-250A 100 kA 125 100 kA 150 125 10,121 100 kA<br />

4089. . .<br />

4103. . .<br />

FWH-250A<br />

or FWH-275A<br />

FWH-250A<br />

or FWH-275A<br />

100 kA 150 100 kA 175 150 10,121 100 kA<br />

100 kA 175 100 kA 200 175 10,121 100 kA<br />

4140. . . FWH-300A 100 kA 225 100 kA 250 225 10,121 100 kA<br />

4168. . .<br />

FWH-325A<br />

or FWH-400A<br />

100 kA 250 100 kA 300 250 10,121 100 kA<br />

4208. . . FWH-500A 100 kA 350 100 kA 400 350 14,657 100 kA<br />

4250. . . FWH-600A 100 kA 400 100 kA 500 400 14,657 100 kA<br />

4302. . . FWH-700A 100 kA 500 100 kA 600 500 14,657 100 kA<br />

4371. . . FWH-800A 100 kA 600 100 kA 700 600 52,800 100 kA<br />

4414. . .<br />

4477. . .<br />

4568. . .<br />

4605. . .<br />

4720. . .<br />

FWH-800A<br />

or FWH-1000A<br />

FWH-1000A<br />

or FWH-1200A<br />

FWH-1000A<br />

or FWH-1200A<br />

FWH-1200A<br />

or FWH-1400A<br />

FWH-1200A<br />

or FWH-1400A<br />

100 kA<br />

100 kA<br />

700<br />

800<br />

100 kA<br />

100 kA<br />

800<br />

900<br />

52,800<br />

52,800<br />

100 kA<br />

100 kA<br />

100 kA 900 100 kA 1000<br />

Not<br />

Applicable<br />

52,800 100 kA<br />

100 kA 1000 100 kA 1200 52,800 100 kA<br />

100 kA 1200 100 kA 1400 52,800 100 kA<br />

1. When semiconductor fuses are used for UL listed drive protection, the drives and fusing must be in the same enclosure. Where multiple semiconductor fuse<br />

ratings are listed for a single drive, <strong>Yaskawa</strong> recommends the larger fuse for cyclical load applications that frequently approach 150% overload. Smaller<br />

semiconductor fuses (than what is listed) of the same manufacturer and series are permitted; however, this may cause fuses to clear prematurely.<br />

2. When using class CC, J, or T fuses as UL listed drive protection, models 4371 and larger have the same enclosure requirements as MCCBs.<br />

3. When using MCCBs, RK1 fuses, or RK5 fuses as UL listed drive protection, the drives must be mounted in ventilated enclosures according to the minimum<br />