Section: Drive Short Circuit Protection \<br />
Table 45: 480 Volt Model Protection Ratings<br />
Semiconductor Fuses<br />
EATON/Bussmann 1<br />
Class CC, J, or T Fuses 2<br />
MCCBs (Molded Case Circuit Breakers)<br />
or Class RK Fuses 3<br />
Drive<br />
Catalog<br />
Code<br />
GA80U . .<br />
Part<br />
Number<br />
Maximum<br />
SCCR<br />
(Fuse-Drive<br />
Combination)<br />
Maximum Fuse<br />
Size (Amps)<br />
Maximum SCCR<br />
(Fuse-Drive<br />
Combination)<br />
Maximum<br />
MCCB Size<br />
(Amps)<br />
Maximum<br />
RK1 or RK5<br />
Fuse Size<br />
(Amps)<br />
Minimum<br />
Enclosure<br />
Volume<br />
(in3)<br />
Maximum<br />
SCCR<br />
(MCCB-Drive<br />
or<br />
RK Fuse-Drive<br />
Combination)<br />
4002. . .<br />
FWH-40B<br />
or FWH-50B<br />
100 kA 3.5 100 kA 15 3.5 4,195 100 kA<br />
4004. . . FWH-50B 100 kA 7 100 kA 15 7 4,195 100 kA<br />
4005. . . FWH-50B 100 kA 9 100 kA 15 9 4,195 100 kA<br />
4007. . . FWH-60B 100 kA 12 100 kA 15 12 4,195 100 kA<br />
4009. . . FWH-60B 100 kA 15 100 kA 15 15 4,195 100 kA<br />
4012. . . FWH-60B 100 kA 20 100 kA 20 20 4,195 100 kA<br />
4018. . . FWH-80B 100 kA 30 100 kA 35 30 4,195 100 kA<br />
4023. . . FWH-90B 100 kA 40 100 kA 45 40 4,195 100 kA<br />
4031. . .<br />
FWH-125B<br />
or FWH-150B<br />
100 kA 50 100 kA 60 50 4,195 100 kA<br />
4038. . . FWH-200B 100 kA 60 100 kA 75 60 4,195 100 kA<br />
4044. . . FWH-200B 100 kA 70 100 kA 80 70 4,195 100 kA<br />
4060. . . FWH-225A 100 kA 100 100 kA 110 100 4,195 100 kA<br />
4075. . . FWH-250A 100 kA 125 100 kA 150 125 10,121 100 kA<br />
4089. . .<br />
4103. . .<br />
FWH-250A<br />
or FWH-275A<br />
FWH-250A<br />
or FWH-275A<br />
100 kA 150 100 kA 175 150 10,121 100 kA<br />
100 kA 175 100 kA 200 175 10,121 100 kA<br />
4140. . . FWH-300A 100 kA 225 100 kA 250 225 10,121 100 kA<br />
4168. . .<br />
FWH-325A<br />
or FWH-400A<br />
100 kA 250 100 kA 300 250 10,121 100 kA<br />
4208. . . FWH-500A 100 kA 350 100 kA 400 350 14,657 100 kA<br />
4250. . . FWH-600A 100 kA 400 100 kA 500 400 14,657 100 kA<br />
4302. . . FWH-700A 100 kA 500 100 kA 600 500 14,657 100 kA<br />
4371. . . FWH-800A 100 kA 600 100 kA 700 600 52,800 100 kA<br />
4414. . .<br />
4477. . .<br />
4568. . .<br />
4605. . .<br />
4720. . .<br />
FWH-800A<br />
or FWH-1000A<br />
FWH-1000A<br />
or FWH-1200A<br />
FWH-1000A<br />
or FWH-1200A<br />
FWH-1200A<br />
or FWH-1400A<br />
FWH-1200A<br />
or FWH-1400A<br />
100 kA<br />
100 kA<br />
700<br />
800<br />
100 kA<br />
100 kA<br />
800<br />
900<br />
52,800<br />
52,800<br />
100 kA<br />
100 kA<br />
100 kA 900 100 kA 1000<br />
Not<br />
Applicable<br />
52,800 100 kA<br />
100 kA 1000 100 kA 1200 52,800 100 kA<br />
100 kA 1200 100 kA 1400 52,800 100 kA<br />
1. When semiconductor fuses are used for UL listed drive protection, the drives and fusing must be in the same enclosure. Where multiple semiconductor fuse<br />
ratings are listed for a single drive, <strong>Yaskawa</strong> recommends the larger fuse for cyclical load applications that frequently approach 150% overload. Smaller<br />
semiconductor fuses (than what is listed) of the same manufacturer and series are permitted; however, this may cause fuses to clear prematurely.<br />
2. When using class CC, J, or T fuses as UL listed drive protection, models 4371 and larger have the same enclosure requirements as MCCBs.<br />
3. When using MCCBs, RK1 fuses, or RK5 fuses as UL listed drive protection, the drives must be mounted in ventilated enclosures according to the minimum<br />
enclosure volume specified. When using MCCBs, <strong>Yaskawa</strong> recommends current limiting type.<br />
<strong>GA800</strong> Selection Guide SL.<strong>GA800</strong>.01, <strong>Yaskawa</strong> America, Inc. 59