Section: Drive Derating \ Altitude<br />
Altitude<br />
Install the drive in a location that with an altitude of 1000 m (3281 ft) or lower. Derate the output current by 1% for each 100 m (328 ft) to install<br />
the drive in altitudes between 1000 m to 3000 m (3281 ft to 9843 ft). It is not necessary to derate the rated voltage in these conditions:<br />
• Installing the drive at 2000 m (6562 ft) or lower. • Installing the drive between 2000 m to 3000 m (6562 ft to 9843<br />
ft) and grounding the neutral point on the power supply.<br />
Contact <strong>Yaskawa</strong> or your nearest sales representative when the drive is not grounded with the neutral network.<br />
Ambient Temperature<br />
Open chassis type (IP20): -10 °C to +50 °C (14 °F to 122 °F)<br />
Enclosed wall-mounted type (Type 1): -10 °C to +40 °C (14 °F to 104 °F)<br />
• Drive reliability is better in environments that do not have wide<br />
temperature fluctuations.<br />
• When installing the drive in an enclosure, use a cooling fan or air<br />
conditioner to keep the internal air temperature in the permitted<br />
range.<br />
• Do not let the drive freeze.<br />
Figure 18: Ambient Temperature Derating Chart<br />
• To install the drive in areas with ambient temperatures 40 °C to<br />
60 °C (104 °F to 140 °F), derate the output current and output<br />
voltage.<br />
<strong>GA800</strong> Selection Guide SL.<strong>GA800</strong>.01, <strong>Yaskawa</strong> America, Inc. 55