Section: <strong>GA800</strong> Configured Package Specifications<br />
Table 46: <strong>GA800</strong> Configured Panel SCCR (Short Circuit Current Rating) for Power Option Combinations<br />
Option Type<br />
With Input Fuse 1<br />
SCCR (Short Circuit Current Rating) of Panel<br />
Without Input Fuse 1<br />
C - 65 kAIC Circuit Breaker 65 kA 65 kA when allowed as a selection<br />
M - 100 kAIC Circuit Breaker 100 kA 100 kA when allowed as a selection<br />
D - Disconnect<br />
100 kA<br />
According to the <strong>GA800</strong> Technical Reference<br />
Short Circuit Protection<br />
E - Standard<br />
Circuit Breaker<br />
J - Dynamic Braking<br />
Overtemp Shutdown<br />
All 240 V: 25 kA<br />
Normal Duty 480 V B002 through B156: 18 kA<br />
Normal Duty 480 V B180 through B720: 35 kA<br />
Heavy Duty 480 V B002 through B180: 18 kA<br />
Heavy Duty 480 V B240 through B590: 35 kA<br />
Same SCCR as with input fuses, but only<br />
when allowed as a selection. Refer to Model<br />
Number Key.<br />
None of the options above<br />
Varies by rating. Consult Factory<br />
1. Some package models with circuit breaker automatically include input fuses. Refer to Model Number Key.<br />
Package Descriptions<br />
Table 47: Configured Option Descriptions<br />
Type 1 ND:<br />
Type 1 HD:<br />
Type 12 ND:<br />
Type 12 HD:<br />
Type 3R ND:<br />
Type 3R HD:<br />
Enclosure/Duty Options<br />
(1) The Normal Duty drive and Configured controls are provided in a Type 1<br />
enclosure, large enough to accommodate any or all of the Configured package<br />
options.<br />
(4) The Heavy Duty drive and Configured controls are provided in a Type 1<br />
enclosure, large enough to accommodate any or all of the Configured package<br />
options.<br />
(2) The Normal Duty drive and Configured controls are provided in a Type 12<br />
enclosure, large enough to accommodate any or all of the Configured package<br />
options.<br />
(5) The Heavy Duty drive and Configured controls are provided in a Type 12<br />
enclosure, large enough to accommodate any or all of the Configured package<br />
options.<br />
(3) The Normal Duty drive and Configured controls are provided in a Type 3R<br />
enclosure, large enough to accommodate any or all of the Configured package<br />
options.<br />
(6) The Heavy Duty drive and Configured controls are provided in a Type 3R<br />
enclosure, large enough to accommodate any or all of the Configured package<br />
options.<br />
Note: The term “Type” (when related to enclosure solutions) refers not only to NEMA Type, but also represents UL Listing for the specific Type(s).<br />
64 <strong>Yaskawa</strong> America, Inc., <strong>GA800</strong> Selection Guide SL.<strong>GA800</strong>.01