Section: Drive Derating \ Single-Phase Derating<br />
Drive Derating<br />
Single-Phase Derating<br />
The <strong>GA800</strong> is optimized for use on three-phase power, but may be derated for use in single-phase to three-phase conversion applications.<br />
Use the table below to select the appropriate drive model based on the AC line and motor voltage.<br />
Table 38: 240 Volt Single-Phase Drive Derating<br />
No<br />
Reactor<br />
With<br />
Reactor<br />
AC Input Type<br />
DC Bus Type<br />
Drive Catalog Code<br />
GA80U . . 1 2<br />
Drive<br />
Output<br />
Capacity<br />
Drive<br />
Output<br />
Capacity<br />
Open Type 1 Enclosed Open Type 1 Enclosed<br />
HP<br />
HP<br />
Part<br />
Number<br />
Part<br />
Number<br />
Part<br />
Number<br />
Part<br />
Number<br />
2004 . . . 1/3 1/2 URX000303 URX000411 URX000043<br />
2006 . . . 1/2 3/4 URX000303 URX000411 URX000043<br />
Not Available<br />
2008 . . . 3/4 1 URX000307 URX000413 05P00620-0113 URX000435<br />
2010 . . . 1 1.5 URX000316 URX000419 05P00620-0115 URX000259<br />
2012 . . . 1.5 2 URX000315 URX000418 05P00620-0115 URX000259<br />
2018 . . . 2 3 URX000319 URX000420 URX000050 Not available<br />
2021 . . . 2 3 URX000323 URX000422 05P00620-0120 URX000261<br />
2030 . . . 2 5 URX000323 URX000422 05P00620-0120 URX000261<br />
2042 . . . 3 7.5 URX000326 URX000424 05P00620-0123 URX000436<br />
2056 . . . 3 7.5 URX000326 URX000424 URX000059 URX000262<br />
2070 . . . 5 10 URX000332 URX000426 URX000063 URX000264<br />
2082 . . . 7.5 10 URX000338 URX000428 URX000072 URX000266<br />
2110 . . . 10 15 URX000338 URX000428<br />
2138 . . . 10 10 URX000338 URX000428<br />
2169 . . . 15 20 URX000344 URX000430<br />
2211 . . . 20 25 URX000347 URX000431<br />
2257 . . . 30 30 Do not use reactor for this rating<br />
Drives 2110 and larger<br />
include integrated DC bus reactor<br />
2313 . . . 30 40 URX000353 URX000433<br />
2360 . . . 40 50 URX000353 URX000433<br />
2415 . . . 50 60 URX000356 URX000434<br />
1. This information reflects derating of three-phase drives for single-phase input applications. Refer to the Single Phase Converter to select a converter that<br />
provides full power (no derating) for some drives when used with single-phase power.<br />
2. Select the partial catalog code from this single-phase table, then refer to the Three-Phase Drive table to select the complete drive catalog code based on<br />
enclosure type.<br />
<strong>GA800</strong> Selection Guide SL.<strong>GA800</strong>.01, <strong>Yaskawa</strong> America, Inc. 51