e installed prior to the installation <strong>of</strong> the ducting. Where stacked plastic<br />

sectional draw pits are <strong>use</strong>d the duct entries shall be drilled to avoid<br />

weakening <strong>of</strong> the structure.<br />

2.04.9 Cables in s<strong>of</strong>t ground<br />

Cables in the s<strong>of</strong>t ground shall be buried in trenches to a minimum<br />

depth <strong>of</strong> 500mm. Where applicable (as detailed in the IEE Wiring<br />

Regulations) cables shall be laid on a bed <strong>and</strong> surround <strong>of</strong> s<strong>and</strong><br />

150mm thick.<br />

Buried cables shall be identified along their entire length in service<br />

trenches with yellow marker tape installed 150mm from ground level.<br />

The marker tape shall labelled “ DANGER – ELECTRIC CABLE<br />

BELOW”<br />

2.04.10 System Management<br />

Individual Mccb protection shall be provided for each control circuit.<br />

A master time clock with battery back-up shall be provided to cut-out the<br />

floodlights at the programmed time. The clock shall allow for the<br />

seasonal changeover from GMT to BST. A key switch for manual<br />

override shall also be provided.<br />

To allow safe egress at the cut-<strong>of</strong>f time, at least one luminaire on each<br />

operational portion <strong>of</strong> the MUGA / STP shall remain in operation for a<br />

five minutes period following cut-<strong>of</strong>f.<br />

The management system shall include a system <strong>of</strong> visual warning to<br />

warn <strong>use</strong>rs the cut-<strong>of</strong>f time is approaching. This shall be achieved by<br />

switching a flashing beacon(s). The beacon shall operate five minutes<br />

before the cut-<strong>of</strong>f time. It shall only operate if any element <strong>of</strong> the<br />

floodlighting is in <strong>use</strong>.<br />

A set <strong>of</strong> manual override switches shall be provided for test <strong>and</strong><br />

emergency control <strong>of</strong> the lights.<br />

A Kwhr meter shall be provided to monitor the total power <strong>use</strong>d by the<br />

floodlights.<br />

An ‘hours run’ facility shall be provided to identify the cumulative time<br />

each group <strong>of</strong> floodlights serving the MUGA / STP has been in<br />

operation.<br />

2.04.11 Small power<br />

26<br />

For info or comments please email mugas@sportengl<strong>and</strong>.org