Out-<strong>of</strong>-service means that a storage tank system or<br />

portion there<strong>of</strong> is no longer serving its intended use.<br />

Overfill protection device means a mechanical<br />

device, electrical device, or fill procedure system<br />

that is intended to prevent a storage tank from<br />

being overfilled.<br />

Owner means the Crown, an institution, corporate<br />

entity, Indian b<strong>and</strong>, government department or<br />

agency, or a person who has legal ownership <strong>of</strong> the<br />

storage tank system or who has been assigned<br />

custody to control, care <strong>for</strong>, manage, or dispose <strong>of</strong><br />

the storage tank system.<br />

Petroleum product means a single product or<br />

mixture <strong>of</strong> at least 70% hydrocarbons, by volume,<br />

refined from crude oil, with or without additives, that<br />

is used, or could be used, as a fuel, lubricant, or<br />

power transmitter <strong>and</strong> without restricting the<br />

<strong>for</strong>egoing, such products include gasoline, diesel<br />

fuel, aviation fuel, kerosine, naphtha, lubricating oil,<br />

fuel oil, engine oil <strong>and</strong> used oil, <strong>and</strong> exclude propane,<br />

paint, <strong>and</strong> solvents.<br />

Piping means fuel conduits, including fittings <strong>and</strong><br />

valves that are necessary <strong>for</strong> the safe h<strong>and</strong>ling<br />

<strong>and</strong> storage <strong>of</strong> petroleum products <strong>and</strong> allied<br />

petroleum products <strong>and</strong> are specified by a nominal<br />

inside diameter.<br />

Precision leak detection test means a test capable <strong>of</strong><br />

detecting a storage tank leak as small as 0.38 L/h<br />

with a probability <strong>of</strong> detection <strong>of</strong> 0.95 or greater <strong>and</strong><br />

a probability <strong>of</strong> false alarm <strong>of</strong> 0.05 or less, within a<br />

period <strong>of</strong> 24 hours, accounting <strong>for</strong> variables such as<br />

vapour pockets, thermal expansion <strong>of</strong> product,<br />

temperature stratification, groundwater level,<br />

evaporation, pressure <strong>and</strong> end deflection.<br />

Pressure liquid media leak detection test means<br />

a test utilizing a device to pressurize piping with a<br />

suitable test liquid to determine the presence<br />

<strong>of</strong> leaks.<br />

Product transfer area means the area around the<br />

connection point between a delivery truck, railcar, or<br />

vessel <strong>and</strong> a storage tank system with a capacity <strong>of</strong><br />

2 500 L or more.<br />

Protected means having impact, projectile, <strong>and</strong> fire<br />

resistance qualities <strong>for</strong> an aboveground storage<br />

tank system.<br />

Protective coating means a coating applied to a<br />

surface to protect the substrate from corrosion.<br />

Secondary containment means an impermeable<br />

barrier that prevents leaks from the primary<br />

storage tank system from reaching outside the<br />

containment area.<br />

Separated solid means the particulate material that<br />

settles at the bottom <strong>of</strong> an oil-water separator.<br />

Site means a lot or property where there is one or<br />

more underground storage tank systems within 100 m<br />

<strong>of</strong> each other, or one or more aboveground storage<br />

tank systems within 200 m <strong>of</strong> each other, <strong>and</strong> all<br />

storage tanks on the property are owned by the<br />

same owner(s).<br />

Sludge means the petroleum or allied petroleum<br />

product residue or material that accumulates at the<br />

bottom <strong>of</strong> a storage tank.<br />

Spill means any loss <strong>of</strong> liquid petroleum or allied<br />

petroleum product from a storage tank system that is<br />

not attributable to a leak in the storage tank system.<br />

Spill containment device means a container fitted to<br />

the inlet <strong>of</strong> a storage tank or to the suction coupling<br />

<strong>of</strong> a used oil storage tank that helps prevent spills<br />

from entering the environment.<br />

Static liquid media leak detection test means a leak<br />

detection test in which a suitable test liquid is placed<br />

into the containment device <strong>and</strong> is monitored <strong>for</strong> a<br />

change in the liquid level <strong>and</strong> the rate <strong>of</strong> change.<br />

Storage tank means a closed container <strong>for</strong> the<br />

storage <strong>of</strong> petroleum or allied petroleum products<br />

with a capacity <strong>of</strong> more than 230 L that is designed<br />

to be installed in a fixed location.<br />

Storage tank system means a system <strong>for</strong> the<br />

storage <strong>and</strong> dispensing <strong>of</strong> petroleum or allied<br />

petroleum product <strong>and</strong> is not limited to storage<br />

tanks, associated piping, vents, pumps, <strong>and</strong><br />

dispensing equipment.<br />

<strong>Environmental</strong> <strong>Code</strong> <strong>of</strong> <strong>Practice</strong> <strong>for</strong> <strong>Aboveground</strong> <strong>and</strong> Underground Storage Tank Systems Containing Petroleum <strong>and</strong> Allied Petroleum Products 4