protection system meets the requirements as<br />
specified in Section 8.6 <strong>and</strong> report in writing<br />
to the authority having jurisdiction the<br />
measured voltage potential(s) <strong>and</strong> whether<br />
or not cathodic protection has been achieved.<br />
4.5.3(1) A new steel storage tank added to an existing<br />
system that already has an impressed current<br />
cathodic protection system shall:<br />
(a) be in con<strong>for</strong>mance with CAN/ULC-<br />
S603-1992, “Underground Steel Tanks”;<br />
<strong>and</strong><br />
(b) be electrically bonded into the impressed<br />
current cathodic protection system. (See<br />
Appendix B, note B.4.5.3(1)(b))<br />
4.5.3(2) When a new storage tank built in<br />
con<strong>for</strong>mance with CAN/ULC-S603.1-1992,<br />
“Galvanic Corrosion Protection Systems <strong>for</strong><br />
Underground Steel Tanks” is installed near<br />
an existing CAN/ULC S603.1-1992,<br />
“Galvanic Corrosion Protection Systems <strong>for</strong><br />
Underground Steel Tanks” storage tank,<br />
precautions shall be taken to ensure both the<br />
new <strong>and</strong> existing tanks are adequately<br />
protected. (See Appendix B, note B.4.5.3(2))<br />
4.5.4(1) Impressed current cathodic protection shall<br />
be interlocked in such a manner that if the<br />
cathodic-protection system is turned <strong>of</strong>f or<br />
bypassed either:<br />
(a) power to the pump will be shut <strong>of</strong>f; or<br />
(b) audible <strong>and</strong> visual alarms will be<br />
turned on.<br />
4.5.5 Impressed current cathodic-protection<br />
systems shall be equipped with a running<br />
time or a downtime totalizer. (See Appendix<br />
B, note B.4.5.5)<br />
4.5.6(1) Cathodically protected storage tanks shall be<br />
installed with:<br />
(a) test wires brought to the surface <strong>and</strong><br />
fastened at an accessible location; or<br />
(b) a permanent reference electrode <strong>and</strong><br />
approved monitoring station, including<br />
test wires <strong>for</strong> each tank.<br />
<strong>Environmental</strong> <strong>Code</strong> <strong>of</strong> <strong>Practice</strong> <strong>for</strong> <strong>Aboveground</strong> <strong>and</strong> Underground Storage Tank Systems Containing Petroleum <strong>and</strong> Allied Petroleum Products 20