DOLD GMBH <strong>Operating</strong> instructions <strong>DMP</strong> <strong>48</strong> <strong>AS</strong> / <strong>AW</strong><br />
"ti.1 " Reset time, control output K 1<br />
0...999 sec.<br />
(adjustment zero = time 0)<br />
"Co.1" = 02, 05<br />
"td.1" Derivative action time, control output K 1 0...500 sec.<br />
(adjustment zero = time 0)<br />
"Co.1" = 02, 05<br />
"CY.1" Cycle time, control output K 1 1...200 sec.<br />
"Co.1" = 02, 05<br />
"HY.1" Hysteresis, control output K 1 0.1...5% of setpoint<br />
range limit<br />
dependent on<br />
sensor ID<br />
"Co.1" = 01, 04<br />
"bd.1" Symmetrical spreading, limit comparator 0.1...99.9 K<br />
K 1 (hysteresis fix at 0.5 K)<br />
"Co.1" = 03, 06<br />
"LA.2" Absolute setpoint, limit-value contact K 2 max. display range<br />
dependent on<br />
sensor ID<br />
"Co.2" = 01, 04<br />
"Lr.2" Spreading, limit-value contact K 2 travel- -99...99.9 K<br />
ing with setpoint<br />
"Co.2" = 02, 05<br />
"bd.2" Symmetrical spreading, limit comparator 0.1...99.9 K<br />
K 2 (hysteresis fix at 0.5 K)<br />
"Co.2" = 03, 06<br />
"HY.2" Hysteresis, limit contact K 2 0.1...20% of setpoint<br />
range limit<br />
dependent on<br />
sensor ID<br />
"Co.2" = 01, 04<br />
8.6 The self-optimization level:<br />
<strong>DMP</strong> <strong>48</strong> <strong>AS</strong> Version: 033 Number of pages: 19 of 25<br />
<strong>DMP</strong> <strong>48</strong> <strong>AW</strong> Edition: 08.08.2006 A0e033.doc<br />
250 sec.<br />
50 sec.<br />
30 sec.<br />
1.0 K<br />
5.0 K<br />
0.0 °C<br />
0.0 K<br />
5.0 K<br />
1.0 K<br />
The <strong>DMP</strong> <strong>48</strong> <strong>AS</strong> / <strong>AW</strong> controller is equipped with an optimization routine for the automatic adaptation<br />
of the controller to the controlled system.<br />
The optimization algorithm is based on modified Ziegler-Nicols rules, according to which the<br />
characteristic data of the system are calculated after an oscillation test in a closed-loop control<br />
circuit.<br />
These characteristic data (particularly period and amplitude of oscillation) form the basis for calculating<br />
specific parameters.<br />
Depending on the control function (heating controller or cooling controller), parameters are calculated<br />
for either the heating or the cooling side.<br />
Starting and aborting optimization:<br />
Optimization can be started or aborted on the self-optimization level (only when function is released).<br />
Optimization optimizes for heating or cooling (heating controller or cooling controller, depending<br />
on configuration).<br />
P Press for approx. 3 sec. to get display: " Cod "<br />
100