Modes<br />

Mode Functions<br />

Winter operation The boiler controls the heating and domestic hot water heating according to the timed<br />

program settings. No decrease in output � The boiler remains at temperature.<br />

Summer operation<br />

Systems without storage<br />

The boiler only controls the domestic hot water heating according to the timed program<br />

settings. No decrease in output �The boiler switches off.<br />

Summer (oil) operation Waste-wood System, Black-pot, Boiler � The boiler is heated by the black-pot.<br />

Transitional operation<br />

Systems without storage<br />

Transitional operation<br />

Systems with stores<br />

NOTE: Systems with stores �<br />

Always select "Transitional<br />

Operation"<br />

Heating for special occasions<br />

Chimney sweep<br />

The boiler produces heat during the set heating phases (parameter menu "boiler<br />

times") (in the morning or the evening, for example). Heating and domestic hot water<br />

heating are regulated according to the set times (heating times, boiler loading). No<br />

decrease in output � Boiler goes to standby. The boiler switches off at the end of the<br />

heating phase.<br />

The boiler switches on during the set store loading times as needed, until the store is<br />

fully loaded�The boiler then switches off.<br />

The boiler switches off at the end of the store loading times, even if the store is not fully<br />

loaded.<br />

NOTE: Make the time window large enough (00:00 to 24:00 hours means: as soon as<br />

the need for heat arises, the boiler loads the store).<br />

The boiler switches on for four hours, the controller is set to "Party Switching,"<br />

domestic water heating is active.<br />

(Starts after pressing and holding the start key (I) for 5 seconds).<br />

The boiler runs for half an hour at full load (all stirrers are opened); then the control unit<br />

switches over to normal heating operation.<br />

(Starts after pressing and holding the "Back" key for 5 seconds; the program can<br />

be ended by pressing the STOP (O) key).<br />

Firewood operation This mode is for firewood-EMERGENCY-operation. The fuel feeding system is not<br />

operational.<br />

Switched off If you press the 0 key, the boiler will switch off according to the shut-down routine. The<br />

system now only regulates the connected heating components<br />

NOTE:<br />

For systems with stores, always select "Transitional Operation"<br />

20 B0310003 Edition 2003