Error message list<br />

Error text Type Cause of error Elimination of the error<br />

35 Return feed temp. LOW W Pump defective, pump too small,<br />

Check the pumps or the sizing of<br />

too long<br />

or heating burden too great<br />

the pumps<br />

36 Safety temperature<br />

S By releasing the EMER-OFF button, Unlock the safety temperature<br />

limiter/EMER-OFF/Pmin<br />

over-heating of the boiler (for example, limiter (white box on the back-<br />

released<br />

heating pump was disengaged or is side of the boiler; only possible<br />

defective, or cutoffs were closed) or by after cooling down the boiler);<br />

releasing the water shortage safety unlock the EMER-OFF button,<br />

device<br />

check system pressure<br />

37 Safety time transpired S The temperature fell below the "Min.<br />

boiler flue gas temp. diff." parameter for a<br />

period longer than the safety time (no<br />

heating material), or the oxygen content Re-fill the heating material in the<br />

is greater than the "Residual oxygen bunker, check the discharge unit<br />

combustion off" parameter, the duration and stoker, break up the bridge<br />

of the under-temperature state is longer in the gravity shaft (first switch<br />

than the safety time (in the HEATING off the system).<br />

state):<br />

material replenishing in the chamber is<br />

too little; bridge formation over the stoker,<br />

the stoker is not feeding<br />

Check stoker drive<br />

38 Over-filling the rotary valve S Only on systems with light-barriers over Open cleaning port cover and<br />

the rotary valve<br />

remove foreign objects or dust<br />

Foreign objects or dust in front of the<br />

light-barrier<br />

from the light-barrier<br />

39 Feeder over-time S Too little heating material in the screw See item 2<br />

40 Outfeed temperature 1<br />

sensing element not OK<br />

41 Outfeed temperature 2<br />

sensing elements not OK<br />

42 Ignition attempt<br />

unsuccessful<br />

43 Discharge screw overflows<br />

too often!<br />

44 Rotary valve overflows too<br />

often<br />

W<br />

W<br />

Signal interrupted, cable or sensing<br />

element defective<br />

Signal interrupted, cable or sensing<br />

element defective<br />

S Boiler remains in "IGNITE" state longer<br />

than the "maximum duration of ignition"<br />

Too little heating material in the<br />

combustion chamber (bunker empty)<br />

Igniter not functioning;<br />

Stoker not feeding<br />

S Clog in the discharge screw; causing the<br />

motor to switch back and forth between<br />

outfeed and return feed<br />

S Clog in the rotary valve; causing the<br />

motor to switch back and forth between<br />

outfeed and return feed<br />

Acknowledge error message;<br />

Boiler starts again<br />

Later, manually feed or ignite in<br />

test mode (CAUTION - igniter<br />

does not automatically switch off<br />

in test mode)<br />

See item 16<br />

See item 21<br />

28 B0310003 Edition 2003