Error message list<br />
Error text Type Cause of error Elimination of the error<br />
35 Return feed temp. LOW W Pump defective, pump too small,<br />
Check the pumps or the sizing of<br />
too long<br />
or heating burden too great<br />
the pumps<br />
36 Safety temperature<br />
S By releasing the EMER-OFF button, Unlock the safety temperature<br />
limiter/EMER-OFF/Pmin<br />
over-heating of the boiler (for example, limiter (white box on the back-<br />
released<br />
heating pump was disengaged or is side of the boiler; only possible<br />
defective, or cutoffs were closed) or by after cooling down the boiler);<br />
releasing the water shortage safety unlock the EMER-OFF button,<br />
device<br />
check system pressure<br />
37 Safety time transpired S The temperature fell below the "Min.<br />
boiler flue gas temp. diff." parameter for a<br />
period longer than the safety time (no<br />
heating material), or the oxygen content Re-fill the heating material in the<br />
is greater than the "Residual oxygen bunker, check the discharge unit<br />
combustion off" parameter, the duration and stoker, break up the bridge<br />
of the under-temperature state is longer in the gravity shaft (first switch<br />
than the safety time (in the HEATING off the system).<br />
state):<br />
material replenishing in the chamber is<br />
too little; bridge formation over the stoker,<br />
the stoker is not feeding<br />
Check stoker drive<br />
38 Over-filling the rotary valve S Only on systems with light-barriers over Open cleaning port cover and<br />
the rotary valve<br />
remove foreign objects or dust<br />
Foreign objects or dust in front of the<br />
light-barrier<br />
from the light-barrier<br />
39 Feeder over-time S Too little heating material in the screw See item 2<br />
40 Outfeed temperature 1<br />
sensing element not OK<br />
41 Outfeed temperature 2<br />
sensing elements not OK<br />
42 Ignition attempt<br />
unsuccessful<br />
43 Discharge screw overflows<br />
too often!<br />
44 Rotary valve overflows too<br />
often<br />
W<br />
W<br />
Signal interrupted, cable or sensing<br />
element defective<br />
Signal interrupted, cable or sensing<br />
element defective<br />
S Boiler remains in "IGNITE" state longer<br />
than the "maximum duration of ignition"<br />
Too little heating material in the<br />
combustion chamber (bunker empty)<br />
Igniter not functioning;<br />
Stoker not feeding<br />
S Clog in the discharge screw; causing the<br />
motor to switch back and forth between<br />
outfeed and return feed<br />
S Clog in the rotary valve; causing the<br />
motor to switch back and forth between<br />
outfeed and return feed<br />
Acknowledge error message;<br />
Boiler starts again<br />
Later, manually feed or ignite in<br />
test mode (CAUTION - igniter<br />
does not automatically switch off<br />
in test mode)<br />
See item 16<br />
See item 21<br />